ABB SPAC 536 C User Manual page 71

Feeder terminal
Table of Contents

Advertisement

Data
Interlocking and Direct Output
Control program
(format; operation, operand)
Event delay; —>10 (open)
Event delay; —>01 (close)
Event delay; —>11 (undefined)
Event delay; —>00 (undefined)
Use of input 10
Use of input 11
Use of input 14
Operation principle of inputs
8...17
Signal output activation via
inputs 8...17
Channel Code
Data
direction
0
M200 RW(e) commands =
:
M300
1...7
S10
RW(e) 0.0, or 0.1...60.0 s
1...7
S11
RW(e) 0.0, or 0.1...60.0 s
1...7
S12
RW(e) 0.0, or 0.1...60.0 s
1...7
S13
RW(e) 0.0, or 0.1...60.0 s
10
S1
RW(e) 0=general mode
11
S1
RW(e) 0=general mode
14
S1
RW(e) 0=general mode
8...17
S2
RW(e) 0=active at low state
8...17
S3
RW(e) 0=no SIGNAL output
Values
LOAD, LOADN
AND, ANDN
OR, ORN
OUT
END
interlocking variables =
status closed (1...7) or
active (8...17)
status undefined (101...107)
status open (201...207)
Output code (20...31)
Special register (60, 61)
L/R key switch position
information (62)
Memory No. (70...89)
variables for Direct Output
Control =
status closed (1...7) or
active (8...17)
status undefined (101...107)
status open (201...207)
Output code (40 or 41,
220...231)
L/R key switch position
information (62)
Memory No. (70...89)
1=ARINH -input
1=pulse counter without
indication
2=pulse counter with indication
1=external AR initiation,
connected to AR1
2=external AR initiation,
connected to AR2
3=external AR initiation,
connected to AR3
1=active at high state
40=SIGNAL5 output is activated
41=SIGNAL6 output is activated
39

Advertisement

Table of Contents
loading

This manual is also suitable for:

Spac 636 c