Block Schematic Diagram - ABB SPAC 536 C User Manual

Feeder terminal
Table of Contents

Advertisement

Block schematic
diagram
4
Fig. 2. Block diagram for the directional neutral current relay module SPCS 3C4.
U
Residual voltage
0
I
Neutral current
0
BS1, BS2, BS3
External blocking signals
BTS1
Blocking signal for the operation of stage Iϕ>
BTS2
Blocking signal for the operation of stage Iϕ>>
BACTRL
External control signal for selection of the operation characteristic I
or I
cosϕ
0
SG1
Front panel selector switchgroup
SG2
Function selector switchgroup for the operation indicators
SGB
Selector switches on the PC board for configuring incoming blocking
signals and outgoing start signals
SS1
Start signal of the low-set stage Iϕ>
TS1
Trip signal of the low-set stage Iϕ>
SS2
Start signal of the high-set stage Iϕ>>
TS2
Trip signal of the high-set stage Iϕ>>
AR1, AR3
Start initiation signals for an optional auto-reclose relay module
Y
Yellow start indicator
R
Red operation indicator
NOTE!
All input and output signals of the directional
neutral overcurrent relay module are not neces-
sarily wired to the terminals of every protection
relay unit incorporating the module. The sig-
nals wired to the terminals are shown in the
paragraph "Signal diagram" in the general
manual of the protection relay.
sinϕ
0