Fault codes
18
Shortly after that the self-supervision system has
detected a permanent internal fault the red IRF
indicator is lit. Simultaneously the relay module
puts forward a control signal to the output relay
of the self-supervision system. In most fault
situations an autodiagnostic fault code appears
on the display of the module. The fault code
consists of a red number 1 (one), and a green,
three digit code number. When a fault is de-
Fault code
Type of fault
4
Output relay control circuit interrupted or output relay module missing
30
Red Only Memory (ROM) damaged
50
Random Access Memory (RAM) damaged
195
Too low a value on reference channel with multiplier 1
131
Too low a value on reference channel with multiplier 5
67
Too low a value on reference channel with multiplier 25
203
Too high a value on reference channel with multiplier 1
139
Too high a value on reference channel with multiplier 5
75
Too high a value on reference channel with multiplier 25
253
No interruptions from the A/D converter
tected the fault code should be recorded for
further use when the relay module is to be
repaired.
Some of the fault codes that may appear on the
display of the directional neutral overcurrent
relay module SPCS 3C4 are shown in the fol-
lowing list: