ABB SPAC 536 C User Manual page 70

Feeder terminal
Table of Contents

Advertisement

38
Data
Contact alarm "AR in progress"
Contact alarm for final trip by AR
initiated by signal AR1
Contact alarm for final trip by AR
initiated by signal AR2
Contact alarm for final trip by AR
initiated by signal AR3
Measuring module
Power measurement
Energy measurement
Configuration and interlocking
Configuration of objects
(format; value 1, value 2,
input No, output code, value 3)
Selection of setting/operation mode
Interlocking selection
Channel Code
Data
direction
0
S80
RW(e) 0=no contact alarm
0
S81
RW(e) 0=no contact alarm
0
S82
RW(e) 0=no contact alarm
0
S83
RW(e) 0=no contact alarm
0
S90
RW(e) 0=no optional module
0
S91
RW(e) 0=no power measurement
0
S92
RW(e) 0=no energy measurement
0
S100
RW(e) 0=freely selectable configu-
0
S101
RW(e) - value 1;
:
S116
0
S198
RW(e) 0=setting mode
0
S199
RW(e) 0=no interlockings
Values
40=alarm via SIGNAL5 output
41=alarm via SIGNAL6 output
40=alarm via SIGNAL5 output
41=alarm via SIGNAL6 output
40=alarm via SIGNAL5 output
41=alarm via SIGNAL6 output
40=alarm via SIGNAL5 output
41=alarm via SIGNAL6 output
1=measuring module 1,
SPTM 8A1
2=measuring module 2 or 3,
SPTM 6A2 or SPTM 6A3
1=power is measured
1=energy is measured
ration and interlocking
program
1... =for future use
0=indicator not used
1=indicator used
- value 2;
0=vertical LEDs indicate open
status
1=vertical LEDs indicate closed
status
- input No;
1...7=input number 1...7
- output code;
0=not controlled object
20...31=output codes 20...31
- value 3;
0=object other than CB
1=object is a CB
1=run mode
1=interlockings in use
2=for future use