ABB SPAC 536 C User Manual page 123

Feeder terminal
Table of Contents

Advertisement

Data to be
transferred over
the serial bus
In addition to the spontaneous data transfer the
SPA bus allows reading of all input data (I-data)
of the module, setting values (S-values), infor-
mation recorded in the memory (V-data), and
some other data. Further, part of the data can
be altered by commands given over the SPA bus.
Data
INPUTS
Measured current on phase L1
Measured current on phase L2
Measured current on phase L3
Measured neutral current
Blocking or control signal
OUTPUTS
Starting of stage I>
Tripping of stage I>
Starting of stage I>>
Tripping of stage I>>
Starting of stage I
>
0
Tripping of stage I
>
0
Starting of stage I
>>
0
started
Tripping of stage I
>>
0
tripped
Signal START1 TS1
Signal START2 SS1
Signal ALARM1 SS2
Signal ALARM2 SS3
Signal TRIP TS2
Operate output relays
All the data are available in channel 0.
R = data to be read from the unit
W = data to be written to the unit
(P) = writing enabled by a password
Code
Data
direction
I1
R
I2
R
I3
R
I4
R
I5
R
O1
R
O2
R
O3
R
O4
R
O5
R
O6
R
O7
R
O8
R
O9
R, W (P)
O10
R, W (P)
O11
R, W (P)
O12
R, W (P)
O13
R, W (P)
O41
R, W (P)
Values
0...63 x I
n
0...63 x I
n
0...63 x I
n
0...210 % I
n
0 = no blocking
1 = external blocking or
control signal active
0 = I> stage not started
1 = I> stage started
0 = I> stage not tripped
1 = I> stage tripped
0 = I>> stage not started
1 = I>> stage started
0 = I>> stage not tripped
1 = I>> stage tripped
0 = I
> stage not started
0
1 = I
> stage started
0
0 = I
> stage not tripped
0
1 = I
> stage tripped
0
0 = I
>>
stage
not
0
1 = I
>> stage started
0
0 = I
>>
stage
not
0
1 = I
>> stage tripped
0
0 = signal not active
1 = signal active
0 = signal not active
1 = signal active
0 = signal not active
1 = signal active
0 = signal not active
1 = signal active
0 = signal not active
1 = signal active
0 = not operated
1 = operated
29