ABB SPAC 536 C User Manual page 29

Feeder terminal
Table of Contents

Advertisement

Data communication
Rear panel
- connection
- fibre optic interface module
- for plastic fibre cable
- for glass fibre cable
Front panel
- connection
Data code
Selectable data transfer rates
Insulation Tests *)
Dielectric test IEC 60255-5
Impulse voltage test IEC 60255-5
Insulation resistance measurement IEC 60255-5
Electromagnetic Compatibility Tests *)
High-frequency (1 MHz) burst disturbance test
IEC 60255-22-1
- common mode
- differential mode
Electrostatic discharge test IEC 60255-22-2 and
IEC 61000-4-2
- contact discharge
- air discharge
Fast transient disturbance test IEC 60255-22-4
and IEC 61000-4-4
- power supply
- I/O ports
Environmental conditions
Specified ambient service temperature
Transport and storage temperature range
Long term damp heat withstand according
to IEC 60068-2-3
Degree of protection by enclosure when panel mounted
Mass of the unit
*) The tests do not apply to the serial port, which is used exclusively for the bus connection module.
RS-485, 9-pole, female
SPA-ZC17BB
SPA-ZC21BB2
SPA-ZC17MM
SPA-ZC21MM
RS 232, 9-pole, female
ASCII
4800 or 9600 Bd
2 kV, 50 Hz, 1 min
5 kV, 1.2/50 µs, 0.5 J
>100 MΩ, 500 Vdc
2.5 kV
1.0 kV
6 kV
8 kV
4 kV
2 kV
-10...+55 °C
-40...+70 °C
<95%, at 40 °C for 56 d
IP 20
about 8 kg
29