Settings

8
The setting values are shown by the right-most
three digits of the display. An indicator close to
the setting value symbol shows when illumi-
I>/I
The operating current of the I> stage as a multiple of the rated current of the protec-
n
tion. Setting range 0.5...5.0 x I
inverse time characteristic.
t>
The operating time of the I> stage, expressed in seconds, when in the definite time
k
mode of operation (SGF1/1-2-3 = 0-0-0). The setting range is 0.05...300 s.
At inverse definite minimum time mode of operation the time multiplier k setting
range is 0.05...1.00.
I>>/I
The starting current of the I>> stage as a multiple of the rated current of the protec-
n
tion. Setting range 0.5...40.0 x I
n - - -) can be selected, with switch SGF2/5, which makes the stage I>> inoperative.
t>>
The operating time of the I>> stage, expressed in seconds. The setting range is
0.04...300 s
I
>/I
The starting current of the I
0
n
tion. Setting range 1.0...25.0 % I
t
>
The operating time of the I
0
0.05...300 s
I
>>/I
The starting current of the I
0
n
tion. Setting range 2.0...200% I
SGF2/6 (displayed as n - - -) can be selected with switch SGF2/6 which makes the
stage I
>> inoperative.
0
t
>>
The operating time of the I
0
0.05...300 s
Further, the checksums of the programming
switchgroups SGF1,SGB and SGR1 are indi-
cated on the display when the indicators adja-
cent to the switchgroup symbols on the front
panel are illuminated. The checksums for
groups SGF2, SGR2 and SGR3 are found in
nated which setting value is indicated on the
display.
at definite time characteristic and 0.5...2.5 x I
n
. Additionally, the setting "infinite" (displayed as
n
> stage as a per cent of the rated current of the protec-
0
.
n
> stage, expressed in seconds. The setting range is
0
>> stage as a percent of the rated current of the protec-
0
. Additionally, the setting "infinite" set by switch
n
>> stage, expressed in seconds. The setting range is
0
the submenus of the corresponding first switch-
group. See further clause "Main menus and
submenus of settings and registers". An exam-
ple of calculating the checksum is given in the
general description of the D-type SPC relay
modules.