Electrical connections

Active digital output wiring

The output current in the HIGH-mode must be limited to 1 mA when the active digital output is used (pas-
sive signal receiver). This is to ensure an output voltage U
> 15 V.
a

Passive digital output wiring

Using the passive output (active signal receiver), the output current in the LOW-mode must be limited to
– 20 mA. This is to ensure an output voltage U
< 2.5 V.
a
5.2.3

Replacement of Sensyflow eco1 measuring systems

Sensyflow eco1 and FMT200-ECO2 (Sensyflow eco2) are compatible. Using the appropriate electrical
adapter, FMT200-ECO2 can be connected to existing plants. As "interface" and "digital output" function-
ality is not available with Sensyflow eco1, there is no wiring within the adapter for these functions.
42/14-41 EN
Thermal Mass Flowmeter FMT200-ECO2