Access Page; Scale Adjust; Set Up Relay Output; Digital Inputs - ABB C1900 series User Manual

Circular chart recorder and recorder/controller
Hide thumbs Also See for C1900 series:
Table of Contents

Advertisement

7.1.6 Set Up Relay Output

As detailed in IM/C1900-PGC, Section 3.5, with the following changes:
Information. Relays can be energized by alarms, logic equation results, digital inputs, control and set point modes, totalizer
wrap signal (totalizer option on model 1953 only).
Select Relay Output
No setup is allowed for relay 1.1 which is assigned to the divert alarm, with polarity set as negative. All relays remain
de-energized for 10 seconds after instrument reset. This holds the instrument in failsafe divert mode.
SELECt
rLY 2. 1
3. 1
4. 1
SOUrCE
rtd Or

7.1.7 Digital Inputs

As detailed in IM/C1900-PGC, Section 3.8.

7.1.8 Set Up Digital Output

As detailed in IM/C1900-PGC, Section 3.6 .

7.1.9 Set Up Analogue Output

As detailed in IM/C1900-PGC, Section 3.7 .

7.1.10 Access Page

As detailed in IM/C1900-PGC, Section 3.9 with the following additional frame which is displayed after the
Tune Password 2 frame:
PEN-AJ
ENbL-Y
N
PA PAS
-
C–PASS
-

7.1.11 Scale Adjust

As detailed in IM/C1900-PGC, Section 3.10 with the following changes:
SELECt
----
Select Relay
Select required relay.
Relay Source
Select the source required to activate the selected relay – refer to IM/C1900, Section 3.5,
Table 3.1 for source description.
rtd Or
(rtd overrange) is an additional source to those listed in Table 3.1.
Pen Adjust
Password frame to allow micrometer adjustment of the red pen.
N
If the password is not enabled (N selected), the micrometer adjustment value is not applied
to position of the red pen.
Y
If the password is enabled (Y selected), pen adjustment is included.
Select micrometer adjust code.
Select Process Variable
Note. No adjustment is available for the True Time Event Pen.
Hot P (I/P1)
Model
Pen 1 (Red)
1951
PV1
1952
PV3
1953
PV3
7 BASIC CONFIGURATION LEVEL
Cold P (I/P2)
Hot W (I/P3)
Pen 2 (Green)
No Pen
PV2
PV2
PV1
PV2
PV1
2
nd
RTD (Aux)
No Pen
PV3
PV4
PV4
15