Maintenance
2 sec.
Enter the maintenance menus.
Date - time
It is only necessary to set the correct date and time in connection with the first use of the
ECL Comfort 110 controller or after a power break of more than 36 hours (see the chapter
on
Adapting the ECL Comfort 110 controller).
Flow temp. (flow temperature control)
Heat curve
The ECL Comfort 110 controls the heating system according to the calculated flow
temperature under the influence of the return and / or room temperature.
The desired flow temperature is defined by 5 settings: 'Temp. max.', 'Temp. min.', 'Slope',
'Displace', and 'Knee point'.
Desired flow temperature
[°C]
110
100
90
80
70
60
50
40
30
20
10
The calculated flow temperature can be influenced by connected sensors, 'Boost' and 'Ramp'
etc.
10 | © Danfoss | 2016.05
-30
-20
-10
0
10
20
[°C]
1000
2000
Heat curve
'Slope'
'Temp. max.'
'Displace'
'Knee point'
'Temp. min.'
Outdoor temp.
VI.KT.G6.02
Need help?
Do you have a question about the ECL Comfort 110 and is the answer not in the manual?
Questions and answers