Cut-Out (Limit For Heating Cut-Out) 5179 - Danfoss ECL Comfort 110 Operating Manual

Application 130
Hide thumbs Also See for ECL Comfort 110:
Table of Contents

Advertisement

Maintenance
Cut-out (limit for heating cut-out)
Set the outdoor temperature limit at which you want the heating system to stop. The
valve closes and after about 3 min. the heating circulation pump stops. 'Temp. min.'
set in line 2177 will be ignored.
Temp.
18 °C
Heating
This function can save energy by stopping the heating system when the outdoor
temperature gets above a set limit. The heating system switches ON again when the
outdoor temperature and the accumulated outdoor temperature become lower than
the set limit.
The heating cut-out is only active when the controller mode is AUTO (scheduled operation).
When the limit value is set to OFF, there is no heating cut-out.
24 | © Danfoss | 2016.05
Setting range
OFF / 1 ... 50 °C
Actual outdoor temp. Accumulated outdoor temp.
Heating OFF
Factory setting
Time
Heating
5179
18 °C
VI.KT.G6.02

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ECL Comfort 110 and is the answer not in the manual?

Table of Contents