Intgr. Time (Time Constant For Room Temp.) 3015; Gain - Max. (Room Temp. Limitation, Max.) 3182; Gain - Min. (Room Temp. Limitation, Min.) 3183 - Danfoss ECL Comfort 110 Operating Manual

Application 130
Hide thumbs Also See for ECL Comfort 110:
Table of Contents

Advertisement

Maintenance
This limitation is based on a PI regulation where P (Gain) responds quickly to deviations
and I (Intgr. time) responds slower and over time removes the small offsets between the
desired and actual values. This is done by changing the desired flow temperature.
Intgr. time (time constant for room temp.)
Controls how fast the room temperature adapts to the desired room temperature (I control).
OFF:
The control function is not influenced by the 'Intgr. time'.
1:
The desired temperature is adapted quickly.
50:
The desired temperature is adapted slowly.
Gain - max. (room temp. limitation, max.)
Determines how much the flow temperature will be influenced (decreased) if the room temperature is
higher than the desired room temperature (P control).
-9.9:
The room temperature has a big influence.
0.0:
The room temperature has no influence.
Gain - min. (room temp. limitation, min.)
Determines how much the flow temperature will be influenced (increased) if the room temperature is
lower than the desired room temperature (P control).
0.0:
The room temperature has no influence.
9.9:
The room temperature has a big influence.
16 | © Danfoss | 2016.05
Setting range
OFF / 1 ... 50
Setting range
-9.9 ... 0.0
Setting range
0.0 ... 9.9
3015
Factory setting
OFF
3182
Factory setting
-4.0
3183
Factory setting
0.0