Maintenance
Application
ECA address (choice of room panel / remote control)
Decides the communication with the room panel or remote control.
OFF:
Room temperature sensor (no room panel / remote control)
A:
Remote control, ECA 61 with address A
B:
Remote control, ECA 61 with address B
P1 exercise (pump exercise)
Exercises the pump to avoid blocking in periods without heat demand.
ON:
The pump is switched ON for 1 minute every third day around noon.
OFF:
The pump exercise is not active.
M1 exercise (valve exercise)
Exercises the valve to avoid blocking in periods without heat demand.
ON:
The valve receives a signal to open and close every third day around
noon.
OFF:
The valve exercise is not active.
Actuator (gear motor / thermo actuator)
Choose the actuator type for your valve.
GEAR:
Gear motor
ABV:
Thermo actuator (Danfoss type ABV)
Control parameters (lines 6174-6187) are overruled if thermo actuator is chosen (ABV).
28 | © Danfoss | 2016.05
Setting range
OFF / A / B
Setting range
ON / OFF
Setting range
ON / OFF
Setting range
GEAR / ABV
7000
7010
Factory setting
OFF
7022
Factory setting
ON
7023
Factory setting
OFF
7024
Factory setting
GEAR
VI.KT.G6.02