Ramp (Reference Ramping) 5013; Optimizer (Optimizing Time Constant) 5014 - Danfoss ECL Comfort 110 Operating Manual

Application 130
Hide thumbs Also See for ECL Comfort 110:
Table of Contents

Advertisement

Maintenance
Ramp (reference ramping)
The time in which the desired flow temperature increases gradually to avoid load peaks in the heat
supply.
Set the ramping time for the controller.
Temp. °C
In order to avoid load peaks in the supply network, the flow temperature can be set to
increase gradually after a period with setback temperature. This causes the valve to open
gradually.
Optimizer (optimizing time constant)
Optimizes the start and stop times for the comfort temperature period to obtain the best comfort at the
lowest energy consumption. The lower the outdoor temperature, the earlier the heating cut-in.
Adjust the optimizing time constant.
The value consists of a two digit number. The two digits have the following meaning:
Left digit
1X
2X
3X
4X
5X
VI.KT.G6.02
Setting range
OFF / 1 ... 99 m
Setting line 5013
Setting range
OFF / 10 ... 59
Heat accumulation of the building
light
medium
heavy
medium
heavy
5013
Factory setting
OFF
Time (min.)
5014
Factory setting
OFF
System type
Radiator systems
Floor heating systems
© Danfoss | 2016.05 | 21