Based On (Optimization Based On Room / Outdoor Temp.) 5020 - Danfoss ECL Comfort 110 Operating Manual

Application 130
Hide thumbs Also See for ECL Comfort 110:
Table of Contents

Advertisement

Maintenance
Right digit
X0
X1
X5
X9
OFF: No optimization. The heating starts and stops at the times set in the
schedule.
Dimensioning temperature:
The lowest outdoor temperature (usually determined by your system designer in connection
with the design of the heating system) at which the heating system can maintain the
designed room temperature.
Example
The system type is radiator, and the heat accumulation of the building is medium.
The left digit is 2.
The dimensioning temperature is -25 °C, and the capacity is normal.
The right digit is 5.
Result:
The setting is to be changed to 25.
It is only possible make use of 'Optimize' if the ECL Comfort 110 controller has a built-in ECA
110 timer program or is connected to an ECA 61.
Based on (optimization based on room / outdoor temp.)
The optimized start and stop time can be based on either room or outdoor temperature.
ROOM: Optimization based on room temperature, if measured.
OUT:
Optimization based on outdoor temperature. Use this setting if the
room temperature is not measured.
22 | © Danfoss | 2016.05
Dimensioning temperature
-50 °C
-45 °C
-25 °C
-5 °C
Setting range
ROOM / OUT
Capacity
large
normal
small
5020
Factory setting
OUT
VI.KT.G6.02