Electrical connections - 24 V a.c. - in general Connecting the temperature sensors and the ECL BUS How to identify your system type Adapting the ECL Comfort 110 controller Manual control Placing the temperature sensors Connecting the room panel / remote control Checklist, electrical connections ..............45...
3183 Limit (return temp. limitation) 4030 18 50 °C Basic principles of application 130 for ECL Comfort 110 Gain - max. (return temp. limitation - max. influence) 4035 19 -2.0 Typically, the flow temperature is always adjusted according to your requirements.
Temperature overview 2 sec. Push the button to see the sensor (S1-S4) temperatures. It is only possible to set the personal schedules if the ECL Comfort 110 controller has a built-in ECA 110 timer program. Change between the temperature displays: ����������������...
Page 6
It is only necessary to set the correct date and time in connection with the first use of the change the start of this period. ECL Comfort 110 controller or after a power break of more than 36 hours (see the chapter Adapting the ECL Comfort 110 controller).
Page 12
5014 Setting range Factory setting It is only possible make use of ‘Optimize’ if the ECL Comfort 110 controller has a built-in ECA OFF / 10 ... 59 110 timer program or is connected to an ECA 61 / 63.
How to identify your system type Adapting the ECL Comfort 110 controller When you switch on the controller the first time, it will ask you to choose language The ECL Comfort controller is a universal controller that can be used for various systems.
Flow temperature sensor (ESMU, ESM-11 or ESMC) Place the sensor max. 15 cm from the mixing point. In systems with heat exchanger, 5 sec. Danfoss recommends that the ESMU-type to be inserted into the exchanger flow outlet. Go to manual mode. Actuator M1 is opening ( �����������...
Page 26
*VIKTG202* Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.