Maintenance
Displace (parallel displacement)
Adjust the parallel displacement of the heat curve with a number of degrees, if required.
Whether it is reasonable to change the 'Slope' (at outdoor temperatures below 0 °C) or
parallel displacement (at outdoor temperatures above 0 °C) will depend on the individual
heat requirement.
Small increases or reductions in the heating temperature can be implemented by means of
the parallel displacement.
Temp. min. (flow temp. limit, min.)
Choose the allowed min. flow temperature for your system. Adjust the factory setting, if
required.
Temp. max. (flow temp. limit, max.)
Choose the allowed max. flow temperature for your system. Adjust the factory setting, if
required.
The setting for 'Temp. max.' has higher priority than 'Temp. min.'.
VI.KT.G6.02
Setting range
-20 ... 20
Setting range
10 ... 150 °C
Setting range
10 ... 150 °C
2176
Factory setting
0
2177
Factory setting
10 °C
2178
Factory setting
90 °C
© Danfoss | 2016.05 | 13
Need help?
Do you have a question about the ECL Comfort 110 and is the answer not in the manual?