Install Vertical Termination Cap; Heat Shield Requirements For Horizontal Termination - Quadra-Fire QFP38-LP Owner's Manual

Installation and operation
Table of Contents

Advertisement

G. Install Vertical Termination Cap
Attach the vertical termination cap by sliding the inner
collar of the cap into the inner fl ue of the pipe section
while placing the outer collar of the cap over the outer
fl ue of the pipe section.
Secure the cap by driving three self-tapping screws
(supplied) through the pilot holes in the outer collar of the
cap into the outer fl ue of the pipe (see Figure 10.15).
Termination Cap
Brackets/
Bolts
Caulk
Figure 10.15
46
(1 of three)
Storm
Collar
Screws
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09
H. Heat Shield Requirements for Horizontal
Termination
WARNING! Risk of Fire!
heat shields must extend through the entire wall thick-
ness.
• DO NOT remove the heat shields attached to the
wall shield fi restop and the horizontal termination
cap.
• Heat shields must overlap 1-1/2 in. (38 mm) mini-
mum.
There are two sections of the heat shield. One section
is factory-attached to the wall shield fi restop. The other
section is factory-attached to the cap. See Figure 10.16.
If the wall thickness does not allow the required 1-1/2 in.
(38 mm) heat shield overlap when installed, an extended
heat shield must be used.
If the wall thickness is less than 4 in./102 mm, the heat
shields on the cap and wall shield fi restop must to be
trimmed. A minimum 1-1/2 in. (38 mm) overlap MUST
be maintained.
Use an extended heat shield if the fi nished wall thickness
is greater than 7-1/4 in. (184 mm).
The extended heat shield may need to be cut to length
maintaining suffi cient length for a 1-1/2 in. (38 mm)
overlap between heat shields.
Attach the extended heat shield to either of the existing
heat shields using the screws supplied with the extended
heat shield. Refer to "Vent Components Diagrams" in
the back of this manual.
Rest the small leg on the extended heat shield on top
of the pipe section to properly space it from the pipe
section.
Important Notice: Heat shields may not be fi eld constructed.
To prevent overheating and fi re,