Chase Top; Install The Termination Cap - Quadra-Fire EPA Certified Woodburning Fireplace 7100FP-GD-B Owner's Manual

Epa certified woodburning fireplace
Hide thumbs Also See for EPA Certified Woodburning Fireplace 7100FP-GD-B:
Table of Contents

Advertisement

R
C. Chase Top
A metal chase top is required to seal the top of the chase
around the chimney pipe. The top should include a turn-
down and drip edge to prevent water from seeping into the
chase. Provide a 1/8 in. (3 mm) gap around the flue pipe
and slope the top downward away from the penetration. See
Figure 29.1.
All seams must be caulked to prevent leaks.
A chase installation must use a chase top. Chase tops are
available from your Quadra-Fire dealer or may be field
constructed.
Attach the chase top to the top of the chase.
Caulk
Figure 29.1 Chase Top Construction
• Chase Top Framing
Framing to top of chase must be constructed to support
service persons, snow load, etc. Maintain 2 in. (51 mm)
clearance to combustibles. Top of framing should be
sheeted with plywood particle board. See Figure 29.2.
Exterior sheeting
Chase top framing
Figure 29.2
September 1, 2008
Termination Cap
2 in. (51 mm) Collar
on Chase Top
Storm Collar
Slope Downward
Turn-down
Drip Edge
Chase
(Chimney)
.018 (26 ga) min.
Galvanized

Chase Top

433-1390G
7100FP EPA Woodburning Fireplace
WARNING
Fire Risk
Never install a single wall slip section or
smoke-pipe in a chase structure.
The higher temperature of this single wall
pipe may radiate sufficient heat to combus-
tible chase materials to cause a fire.
D. Install the Termination Cap
Note: To protect against the effect of corrosion on those
parts exposed to the weather, the termination cap can be
painted with a rust-resistant paint.
WARNING
Fire Risk
The minimum overlap of cap to pipe
MUST be met or chimney may separate
from cap.
Separation allows sparks, heat and embers
to escape.
Install the chimney sections up through the chase
enclosure. When using a Round Termination Cap, the
uppermost top section of pipe must extend 6 in. (152 mm)
above the top of the flashing collar to allow installation of
the storm collar and termination cap. See Figure 29.3.
Minimum 1-1/2 in. (38 mm) overlap of cap over pipe
6 in. (152mm) min.
Flashing Collar
Figure 29.3 Installing a TR344 Round Termination Cap
For installations utilizing a Round Telescoping Termination
Cap, the uppermost chimney section must be below the
top of the chase top, but not more than 14-1/2 in. (368 mm)
below the top of the chase top. Minimum overlap of
chimney and termination cap must be 1-1/2 in. (38 mm).
See Figure 30.1 on page 30.
Storm Collar
2 in. (51 mm) min.
2 in. (51 mm) min. collar