2. Top Vent - Vertical Termination
No Elbow
Figure 7.6
Two Elbows
Figure 7.7
36
12 ft (3.66 m) min.
60 ft (18.29 m) max.
12 ft (3.66 m) min.
60 ft (18.29 m) max.
Maximum horizontal
run is 100% of
vertical, but cannot
exceed 18 ft (5.49 m)
Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09
Note: If installing a vertical vent/
termination off the top of the ap-
pliance, the fl ue restrictor should
be used. See Section 15.J. for
damper adjustment.
1 ft m (.30 m) min.