Dantherm CDP 50 Service Manual page 52

Hide thumbs Also See for CDP 50:

Advertisement

EN
RS-485 Interface
Continued
52
Database
Register Byte
parameter
Evap_
temp2
12
(decimal)
7
Evap_
temp2
13
(fraction)
Cond_
14
temp1
(decimal)
8
Cond_
temp1
15
(fraction)
Aux_temp
16
(decimal)
9
Aux_temp
17
(fraction)
Amb_temp
18
(decimal)
10
Amb_temp
19
(fraction)
Amb_hum
20
(High byte)
11
21
22
RH_set
12
23
RH_Fan
Temp_set
24
(decimal)
13
Temp_set
25
(fraction)
30
Fail_start
16
31
SB_mode
32
DEH_mode
17
33
Ice_mode
De-
Min
Max
Description
fault
-40
100
0
Temperature from evaporator 2:
Usage the same as above.
-40
100
0
-40
100
0
Temperature from condenser:
Usage the same as above.
-40
100
0
-40
100
0
Temperature from auxiliary sensor:
Usage the same as above.
-40
100
0
-40
100
0
Temperature of ambient air:
Usage the same as above.
-40
100
0
Humidity of ambient air:
0
100
0
High byte has no meaning and always contains zero.
Only low byte can be used.
40
95
40
Setpoint value of desired humidity.
40
95
40
Setpoint value of humidity for exhaust fan start.
Setpoint value of desired temperature:
0
36
0
Usage the same as for Evap_temp1.
0
1
0
State of Fail_start mode
0
1
0
Stand-by mode state
0
1
0
Dehumidifying state
0
1
0
Deicing state