Service guide
Introduction
Monthly service
Annual service
The dehumidi er requires very little attention for trouble free running. All the necessary safety
and control functions have been built in. The fan motor(s) and the compressor have permanent
lubrication and require no particular maintenance.
The air inlet lter is to be cleaned once a month. The lter is placed in a stand behind the grill in
the air inlet duct. Also drip tray and outlet should be cleaned so that water can run o freely.
Please follow this procedure to perform the monthly service:
Step
Action
1
Unlock the two locks underneath the dehumidi er
2
Dismount the front cap by lifting it up and take out the lter.
The lter is located on the rear of the front cap
3
Wash the lter in tepid soapy water or vacuum clean thoroughly.
If the lter is faulty, replace it.
4
Insert lter in the lter holder, reattach the cap and lock the two locks. (From Step 1)
The dehumidi er should be inspected once a year.
Please follow this procedure to perform the annual service:
Step
Action
1
Remove the front from the dehumidi er
2
Inspect the inside of the dehumidi er
3
Vacuum clean the dehumidi er to remove any dust or debris
Important: Vacuum clean the condenser thoroughly
4
If necessary wash the lamella evaporator in tepid soapy water if it is badly soiled
EN