Dantherm CDP 50 Service Manual page 46

Hide thumbs Also See for CDP 50:

Advertisement

EN
Alarms continued
High pressure fail
Service alarm
Press for 5 seconds
to enter installer
menu setup
Alarms priority
46
Dehumidi er has stopped because of High Pressure detection.
Fail can not be dismissed from Remote panel.
It is not allowed to enter menu setup for modi cation of set points values.
The Service icon will be shown when it is time for servicing the dehumidi er.
The service alarm does not a ect the operation of dehumidi er.
To dismiss/reset service alarm:
- Press right for 5 seconds to enter the installer menu.
- Press DOWN/UP to navigate to service icon.
- Press RIGHT/LEFT to change setpoint from 0 to desired service interval.
- Con rm service interval by pressing enter.
HP
High priority
LP
SEnS
Abt
Low priority
Abrh
When more than one alarm is active the list above
shows the priority of the alarms.