2 Nomenclature and Installation
2-3-5

Connecting Communications Cables and Connectors

Use straight connections for the communications cables and connectors, as shown below.
Wire color
Pin No.
1
White-Green
2
Green
3
White-Orange
4
Blue
5
White-Blue
6
Orange
7
White-Brown
8
Brown
*1
Hood
Shield
*1. Connect the cable shield wire to the connector hood at both ends of the cable.
Additional Information
There are two connection methods for Ethernet cables: T568A and T568B.
The T568A connection method is shown in the above figure, but the T568B connection method
can also be used.
2-3-6

Connecting Communication Cables to Units

Cable connections can be made freely in EtherCAT networks.
The following example shows daisy-chain connections.
Connect the communications cable from the EtherCAT master to the input port on the EtherCAT Slave
Unit, and then connect another communications cable from the output port on the EtherCAT Slave Unit
to the input port on the next EtherCAT slave.
Do not connect anything to the output port of the EtherCAT slave at the end of the network.
2 - 12
CJ-series EtherCAT Slave Units Operation Manual for NJ-series CPU Unit (W542)
Wire color
Pin No.
White-Green
1
Green
2
White-Orange
3
Blue
4
White-Blue
5
Orange
6
White-Brown
7
Brown
8