To isolate faults when the tester shows limited
wire map information, turn off the AC wire map
test, then do tests on the cabling after the PoE
device. Also do a test on the patch cord that
connects the PoE device to the link.
Open
Open on pair 4,5. The open is 17 m
from the tester and 1.8 m from the
remote. The open is on one or both
wires.
Figure 49. AC Wire Map Examples: Open and Short
Chapter 4: Test Twisted Pair Through a PoE Device
Note
GPU150.PNG
Short between pairs 1,2 and 3,6.
The short is 5 m from the remote.
The short is between two, three,
or all four wires.
AC Wire Map Results
GPU151.PNG
Short
101