Atlas Copco GA 5 Instruction Book

Atlas Copco GA 5 Instruction Book

Oil-injected rotary screw compressors
Hide thumbs Also See for GA 5:
Table of Contents

Advertisement

Quick Links

Atlas Copco
Oil-injected rotary screw compressors
GA 5, GA 7, GA 11
Instruction book

Advertisement

Table of Contents
loading

Summary of Contents for Atlas Copco GA 5

  • Page 1 Atlas Copco Oil-injected rotary screw compressors GA 5, GA 7, GA 11 Instruction book...
  • Page 3 Atlas Copco Oil-injected rotary screw compressors GA 5, GA 7, GA 11 From following serial No. onwards: CAI 700 000 Instruction book Original instructions Copyright notice Any unauthorized use or copying of the contents or any part thereof is prohibited.
  • Page 4: Table Of Contents

    Instruction book Table of contents Safety precautions......................7 ...........................7 AFETY ICONS ......................7 AFETY PRECAUTIONS GENERAL ...................7 AFETY PRECAUTIONS DURING INSTALLATION ....................9 AFETY PRECAUTIONS DURING OPERATION .................10 AFETY PRECAUTIONS DURING MAINTENANCE OR REPAIR General description......................12 ..........................12 NTRODUCTION ............................16 IR FLOW ............................17 IL SYSTEM ..........................18 OOLING SYSTEM ........................19...
  • Page 5 Instruction book 3.10 ......................39 ALLING UP RUNNING HOURS 3.11 .......................40 ALLING UP MOTOR STARTS 3.12 .......................41 ALLING UP MODULE HOURS 3.13 ......................41 ALLING UP LOADING HOURS 3.14 ........................41 ALLING UP LOAD RELAY 3.15 ..................42 ALLING UP RESETTING THE SERVICE TIMER 3.16 ................43 ELECTION BETWEEN LOCAL...
  • Page 6 Instruction book ..........................76 ALLING UP MENUS ...........................77 NPUTS MENU ..........................78 UTPUTS MENU ............................80 OUNTERS ..........................81 ERVICE MENU 4.10 ..........................85 ETPOINT MENU 4.11 ........................87 VENT HISTORY MENU 4.12 ......................88 ODIFYING GENERAL SETTINGS 4.13 ............................89 NFO MENU 4.14 ...........................90 EEK TIMER MENU 4.15 .............................99 EST MENU...
  • Page 7 Instruction book ........................137 URING OPERATION ........................139 HECKING THE DISPLAY ............................140 TOPPING ......................141 AKING OUT OF OPERATION Maintenance........................143 ....................143 REVENTIVE MAINTENANCE SCHEDULE ........................146 IL SPECIFICATIONS ......................146 TORAGE AFTER INSTALLATION ..........................147 ERVICE KITS ......................147 ISPOSAL OF USED MATERIAL Adjustments and servicing procedures..............148 ..........................148 RIVE MOTOR ............................148...
  • Page 8 Instruction book 11.7 ® ..................169 ECHNICAL DATA LEKTRONIKON CONTROLLER Instructions for use....................171 Guidelines for inspection...................172 Pressure equipment directives.................173 Declaration of conformity..................174 2920 7090 51...
  • Page 9: Safety Precautions

    Instruction book Safety precautions Safety icons Explanation Danger for life Warning Important note Safety precautions, general General precautions 1. The operator must employ safe working practices and observe all related work safety requirements and regulations. 2. If any of the following statements does not comply with the applicable legislation, the stricter of the two shall apply.
  • Page 10 Instruction book Precautions during installation 1. The machine must only be lifted using suitable equipment in accordance with the applicable safety regulations. Loose or pivoting parts must be securely fastened before lifting. It is strictly forbidden to dwell or stay in the risk zone under a lifted load. Lifting acceleration and deceleration must be kept within safe limits.
  • Page 11: Safety Precautions During Operation

    Instruction book Safety precautions during operation All responsibility for any damage or injury resulting from neglecting these precautions, or non-observance of the normal caution and care required for installation, operation, maintenance and repair, even if not expressly stated, will be disclaimed by the manufacturer.
  • Page 12: Safety Precautions During Maintenance Or Repair

    Instruction book Safety precautions during maintenance or repair All responsibility for any damage or injury resulting from neglecting these precautions, or non-observance of the normal caution and care required for installation, operation, maintenance and repair, even if not expressly stated, will be disclaimed by the manufacturer.
  • Page 13 Instruction book • Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin with water. If liquid refrigerant contacts the skin through clothing, never tear off or remove the latter; flush abundantly with fresh water over the clothing until all refrigerant is flushed away; then seek medical first aid.
  • Page 14: General Description

    Workplace compressors have no dryer, while Workplace Full-Feature (FF) compressors are provided with an integrated air dryer. The basic version of GA 5 up to GA 11 is equipped with an Elektronikon controller ( see section Elektronikon controller). The Elektronikon® Graphic controller is available as option (see section Elektronikon graphic controller).
  • Page 15 Instruction book Front view, Workplace tank-mounted with Elektronikon® controller Ref. Name Air receiver Air outlet valve Automatic condensate outlet OSD drain outlet (option) Manual condensate drain valve Manual condensate drain valve Elektronikon® controller Emergency stop button Electric cable entry 2920 7090 51...
  • Page 16 Instruction book Floor-mounted version The compressors are installed directly on the floor. GA 11 Pack, Floor mounted, Front view Elektronikon® controller Emergency stop button Manual condensate drain valve Automatic condensate outlet 2920 7090 51...
  • Page 17 Instruction book Floor-mounted Workplace Pack compressor, rear view Ref. Name Air filter Air outlet valve Combicooler Fan motor Drive motor 2920 7090 51...
  • Page 18: Air Flow

    Instruction book Air flow Flow diagrams For Workplace units For Workplace Full-Feature units References Ref. Description Intake air Air/oil mixture Hot compressed air 2920 7090 51...
  • Page 19: Oil System

    Instruction book Ref. Description Dry air Condensate Dry air (compressors with integrated dryer) Description Air drawn through filter (AF) and open inlet valve (IV) into compressor element (E) is compressed. Compressed air and oil flow into the air receiver/oil separator (OT). The air flows through minimum pressure valve (Vp) to air cooler (Ca).
  • Page 20: Cooling System

    Instruction book References Description Intake air Air/oil mixture Compressed air Description The air/oil mixture coming from the compressor element flows into the oil separator/tank, where most of the oil is separated by centrifugal action. The oil collects in the lower part of air receiver/oil separator (OT) which serves as oil tank.
  • Page 21: Condensate System

    Instruction book References Description Intake air Compressed air/oil Compressed air Description The cooling system comprises of air cooler (Ca) and oil cooler (Co). The cooling air is generated by a fan (FN). The fan is set on the shaft of the motor. Condensate system Condensate drains Condensate drains on a floor-mounted version...
  • Page 22: Regulating System

    Instruction book Regulating system Flow diagram Unloading If the air consumption is less than the air output of the compressor, the net pressure increases. When the net pressure reaches the unloading pressure, solenoid valve (Y1) is de-energised. • The control pressure present in the chambers of loading plunger (LP) and unloading valve (UV) is vented to atmosphere via solenoid valve (Y1).
  • Page 23: Electrical Diagrams

    Instruction book Electric cabinet Reference Description Fuses F2-F3 Fuses Overload relay, compressor motor Delta contactor Star contactor Line contactor Transformer Earth terminal Electrical diagrams The service diagram and the explanatory designations below are given as typical example only. Some of the texts may not be applicable to a specific case. The applicable service diagram is situated in the electric cubicle of the compressor.
  • Page 24 Instruction book Service diagram Designations 2920 7090 51...
  • Page 25 Instruction book Reference Sensors / solenoid valves / electronic water drain PT20 Pressure sensor, air outlet TT11 Temperature sensor, element outlet TT90 Temperature sensor, dew-point (Full Feature) TT91 Temperature sensor, ambient (Full Feature) Loading solenoid valve Reference Motors Compressor motor Fan motor, cooler Reference Electric cabinet...
  • Page 26: Air Dryer

    Instruction book Reference Optional equipment R1/K34 Drive motor thermistor protection, shut-down Anti-condensation heaters Auxiliary relay, load/unload signal for ES100 Main power isolating switch Solenoid valve for modulating control Air dryer Flow diagram Air dryer Reference Name Air inlet Air outlet Air/air heat exchanger Air/refrigerant heat exchanger/evaporator Condensate separator...
  • Page 27 Instruction book Reference Name Refrigerant condenser Liquid refrigerant dryer/filter Capillary Hot gas by-pass valve Condenser cooling fan Pressure switch, fan control Compressed air circuit Compressed air enters heat exchanger (1) and is cooled by the outgoing, cold, dried air. Water in the incoming air starts to condense.
  • Page 28: Elektronikon® Controller

    Instruction book Elektronikon® controller ® Elektronikon regulator Control panel Introduction ® In general, the Elektronikon regulator has following functions: • Controlling the compressor • Protecting the compressor • Monitoring components subject to service • Automatic restart after voltage failure (made inactive) Automatic control of the compressor The regulator maintains the net pressure between programmable limits by automatically loading and unloading the compressor.
  • Page 29: Control Panel

    The regulator has a built-in function to automatically restart the compressor when the voltage is restored after voltage failure. This function is deactivated in compressors leaving the factory. If desired, the function can be activated. Consult the Atlas Copco Customer Centre. If activated, and if the regulator was in the automatic operation mode, the compressor will...
  • Page 30: Icons Used On The Display

    Instruction book Reference Designation Function LED, Service Is lit when service is needed. Start button This button starts the compressor. Automatic operation LED (3) lights up. The Elektronikon is operative. Stop button This button is used to stop the compressor. Automatic operation LED (3) goes out.
  • Page 31 Instruction book Function Icon Description Units Pressure unit (Mega Pascal) Pressure unit (pounds per square inch) Pressure unit (bar) Temperature unit Temperature unit Hours (always shown together with seconds) Percent The value shown must be multiplied by 10 to get the actual value The value shown must be multiplied by 100 to get the actual value...
  • Page 32: Main Screen

    The Main screen shows: • The compressor status by means of pictographs • The air outlet pressure Always consult Atlas Copco if the pressure on the display is preceded by a "t". Shut-down warning Description A shut-down warning will appear in the event of: •...
  • Page 33: Dewpoint Temperature

    Instruction book • Press Scroll down button (12). The screen shows the temperature at the compressor element outlet: The screen shows that the temperature at the element outlet is 122 °C It remains possible to scroll through other screens, using the Scroll buttons up and down (12) to check the actual status of other parameters.
  • Page 34: Shut-Down

    Instruction book Warning screen, dewpoint temperature The screen shows that the dewpoint temperature is 9˚C. • It remains possible to scroll through other screens (using Scroll buttons 12) to check the actual status of other parameters. • Press button (11) to stop the compressor and wait until the compressor has stopped. •...
  • Page 35: Service Warning

    Instruction book • Press Scroll buttons (12) until the actual compressor element temperature appears. Shut-down screen, element outlet temperature The screen shows that the temperature at the outlet of the compressor element is 122 ˚C. • Switch off the voltage and remedy the trouble. •...
  • Page 36 In the example above, carry out all service operations belonging to the 8000 running hours interval as well as those belonging to the 4000 running hours interval. • If using mineral oil instead of Atlas Copco Roto-Inject Fluid, the service timer has to be decreased. See section Preventive maintenance schedule. 2920 7090 51...
  • Page 37: Scrolling Through All Screens

    Instruction book • After servicing, reset the service timer. See section Calling up/resetting the service timer Scrolling through all screens Control panel Control panel Scroll buttons (12) can be used to scroll through all screens. The screens are divided into register screens, measured data screens, digital input screens (numbered as <d.in>, <d.1>, ...), parameter screens (numbered as <P.01>, <P.02>, ...), protections screens (numbered as <Pr.01>,...) and test screens (numbered as <t.01>,...).
  • Page 38 Instruction book Digital input Designation Related topic screens <d.4> Loading hours (hrs or x1000 hrs) See section Calling up loading hours <d.5> Load relay (x1 or x 1000) See section Calling up Calling up load relay <d.6> Service timer reading (hrs or x 1000 hrs) See section Calling up/resetting the service timer...
  • Page 39 Instruction book Test screens Designation Related topic <t.01> Display test See sections Test screens <t.02> Safety valve test See sections Test screens <t.03> Production test See sections Test screens Menu flow Simplified menu flow 2920 7090 51...
  • Page 40: Calling Up Outlet And Dewpoint Temperatures

    Instruction book Ref. Description Ref. Description Compressor outlet pressure (16) Pressure band setting Compressor outlet temperature (17) Service timer settings Dewpoint temperature (18) Temperature unit Digital input status (19) Unit pressure Running hours (20) Auto restart Motor starts (21) Selection Y-D/DOL Module hours (22) Load delay time...
  • Page 41: Calling Up Running Hours

    Instruction book The screen shows that the outlet temperature is 82 ˚C. • For Full-Feature compressors: Press Scroll button (12). The dewpoint temperature will be shown: The screen shows that the dewpoint temperature is 3 ˚C. • Press Scroll button (12) to scroll downwards or upwards through the screens. 3.10 Calling up running hours Control panel Starting from the Main screen:...
  • Page 42: Calling Up Motor Starts

    Instruction book The screen shows the unit used (x1000 hrs) and the value (11.25): the running hours of the compressor are 11250 hours. 3.11 Calling up motor starts Control panel Starting from the Main screen: • Press Scroll button (12) until <d.2> is shown and then press Enter button (13): This screen shows the number of motor starts (x 1 or - if <x1000>...
  • Page 43: Calling Up Module Hours

    Instruction book 3.12 Calling up module hours Control panel Starting from the Main screen: • Press Scroll button (12) until <d.3> is shown and then press Enter button (13): In the example shown, the screen shows the unit used (hrs) and the value (5000): the regulator module has been in service during 5000 hours.
  • Page 44: Calling Up/Resetting The Service Timer

    Instruction book • Press Scroll button (12) until <d.5> is shown and then press Enter button (13): This screen shows the number of unload to load actions (x 1 or - if <x1000> lights up - x 1000). In the above example, the number of unload to load actions is 10100.
  • Page 45: Selection Between Local, Remote Or Lan Control

    Instruction book This screen shows the unit used <hrs> (or <x1000 hrs>) and the value <1191>. In the example shown, the compressor has run 1191 hours since the previous service. Resetting the service timer After servicing, see section Service warning, the timer has to be reset: •...
  • Page 46 Instruction book If necessary enter the password. The next screen shows that the function is “ON or OFF” Press the Enter button (13) to change this mode Use the Scroll buttons (12) to select ON or OFF. When this function is ON, use the Scroll buttons up or down (12) to see the node ID. If desired the user can change this ID.
  • Page 47: Calling Up/Modifying Ip, Gateway And Subnetmask

    Instruction book Press the Enter button (13) to modify the setting. The utmost left value will blink. Change this value by using the Scroll buttons (12). Press the Enter button (13) to confirm. Change the other values in the same way, as required.
  • Page 48 Instruction book Modification Press the Enter button (13) and if necessary enter the password. The first digits are blinking. Use the Scroll buttons Up or Down (12) to modify the settings and press Enter (13) to confirm. Modify the next digits the same way.
  • Page 49: Calling Up/Modifying Pressure Band Settings

    Instruction book 3.19 Calling up/modifying pressure band settings Calling up the settings Starting from the Main screen: • Press Scroll button (12) until <P.04> is shown and then press Enter button (13). Pressure band 1 (<Pb.1>) is shown on the display. Button (12) can be used to scroll to pressure band 2 (<Pb.2>). •...
  • Page 50: Modifying The Pressure Band Selection

    Instruction book Loading pressure Unloading pressure • Press Enter button (13) to modify the load level (value starts blinking). A password may be required. Use Scroll buttons (12) to change the loading pressure. • Press Enter button (13) to program the new values or press the Escape button (14) to cancel. 3.20 Modifying the pressure band selection Control panel 2920 7090 51...
  • Page 51: Calling Up/Modifying Service Timer Settings

    Instruction book Starting from the Main screen: • Press Scroll button (12) until <P.05> is shown and then press Enter button (13). The active pressure band 1 (<Pb.1>) is shown on the display. • Press Enter button (13) to modify the pressure band selection (a password may be required). The active pressure band <Pb.1>...
  • Page 52: Calling Up/Modifying Unit Of Pressure

    3.24 Activating automatic restart after voltage failure Description This parameter, accessible in screen <P.09>, can only be modified after entering a code. Consult Atlas Copco if this function is to be activated. 3.25 Selection between Y-D or DOL starting...
  • Page 53: Calling Up Modifying Load Delay Time

    Instruction book • This parameter can only be modified after entering a code. Consult Atlas Copco if the parameter is to be changed. 3.26 Calling up modifying load delay time Control panel Starting from the Main screen: • Press Scroll button (12) until <P.11> and the compressor load pictograph is shown and press the Enter button (13): •...
  • Page 54: Activating Password Protection

    Instruction book • Press the Scroll button (12) until <P.12> and the motor pictograph is shown and press the Enter button (13): • This screen shows the minimum stop time (20) and the unit <s> (seconds). • To modify this value press the Enter button (13). The value starts blinking and Scroll buttons (12) can be used to modify this value.
  • Page 55: Calling Up/Modifying Protection Settings

    Instruction book • Press the Enter button (13). • The function of this screen is to activate the remote load/unload relay. To be able to activate this remote Load/Unload functionality, a physical digital input with function Load/Unload is required. Once this parameter is activated, the physical digital input can be used to switch the compressor between Load and Unload.
  • Page 56 Instruction book • A low warning level, shown on the display as <AL-L>. • A high warning level, shown on the display as <AL-H>. • A low shut-down level, shown on the display as <Sd-L>. • A high shut-down level, shown on the display as <Sd-H>. •...
  • Page 57: Test Screens

    Safety valve test In the test screen <t.02> a safety valve test is provided. The safety valves can only be tested after entering a code. Consult Atlas Copco if the safety valves are to be tested. Production test Test screen <t.03> is only intended for production test. If the Main screen shows following screen, the...
  • Page 58: Web Server

    Instruction book 3.32 Web server All Elektronikon controllers have a built-in web server that allows direct connection to a PC via a local area network (LAN). This allows to consult certain data and settings via the PC instead of via the display of the controller.
  • Page 59 Instruction book • Click on View Network connections (1). • Select the Local Area connection (1), which is connected to the controller. • Click with the right button and select properties (1). 2920 7090 51...
  • Page 60 Instruction book • Use the checkbox Internet Protocol (TCP/IP) (1) (see picture). To avoid conflicts, de-select other properties if they are selected. After selecting TCP/IP, click on the Properties button (2) to change the settings. • Use the following settings: •...
  • Page 61 Instruction book • Click on the Connections tab (1) and then click on the LAN settings button (2). • In the Proxy server Group box, click on the Advanced button (1). 2920 7090 51...
  • Page 62 Instruction book • In the Exceptions Group box, enter the IP address of your controller. Multiple IP addresses can be given but they must be separated with semicolons (;). Example: Suppose that you already added two IP addresses (192.168.100.1 and 192.168.100.2). Now you add 192.168.100.100 and separate the 3 IP addresses by putting semicolons between them (1) (see picture).
  • Page 63 Instruction book Navigation and options • The banner shows the compressor type and the language selector. In this example, three languages are installed on the controller. • On the left site of the interface you can find the navigation menu (see picture below). If a license for ESi is foreseen, the menu contains 3 buttons.
  • Page 64 Instruction book Compressor settings All compressor settings can be hidden or shown. Put a mark for each setting. Only the machine status is fixed and can not be removed from the main screen. Analog inputs (The units of measure can be changed in the preference button from the navigation menu). Counters Counters give an overview of all actual counters from controller and compressor.
  • Page 65 Instruction book Digital outputs Shows a list of all digital outputs and their status. Special protections Give an overview of all special protections of the compressor. Service plan Shows all levels of the service plan and status. This screen only shows the running hours. It is also possible to show the actual status of the service interval.
  • Page 66: Programmable Settings

    Instruction book A possible ESi screen 3.33 Programmable settings Parameters: unloading/loading pressures for compressors without built-in refrigeration dryer Minimum Factory Maximum setting setting setting Unloading pressures Unloading pressure (7.5 bar compressors) bar(e) Unloading pressure (7.5 bar compressors) psig 101.5 108.8 Unloading pressure (8.5 bar compressors) bar(e) Unloading pressure (8.5 bar compressors)
  • Page 67 Instruction book Minimum Factory Maximum setting setting setting Loading pressure (13 bar compressors) psig 172.6 187.1 Loading pressure (100 psi compressors) bar(e) Loading pressure (100 psi compressors) psig 91.4 105.9 Loading pressure (125 psi compressors) bar(e) Loading pressure (125 psi compressors) psig 130.5 Loading pressure (150 psi compressors)
  • Page 68 Also see section Preventive maintenance schedule. Consult Atlas Copco if a timer setting has to be changed. See section Calling up/modifying service timer settings. The intervals must not exceed the nominal intervals and must coincide logically. 2920 7090 51...
  • Page 69 Minimum stop Once the compressor has automatically stopped, it will remain stopped for the minimum time stop time, whatever happens with the net air pressure. Consult Atlas Copco if a setting lower than 20 seconds is required. Unloading/ The regulator does not accept illogical settings, e.g. if the unloading pressure is Loading pressure programmed at 7.0 bar(e) (101 psi(g)), the maximum limit for the loading pressure changes...
  • Page 70: Elektronikon® Graphic Controller

    Instruction book Elektronikon® Graphic controller ® Elektronikon Graphic controller Control panel ® Display of the Elektronikon Graphic controller Introduction The Elektronikon controller has following functions: • Controlling the compressor • Protecting the compressor • Monitoring components subject to service • Automatic restart after voltage failure (made inactive) Automatic control of the compressor operation The regulator maintains the net pressure between programmable limits by automatically loading and unloading the compressor.
  • Page 71: Protecting The Compressor

    The regulator has a built-in function to automatically restart the compressor if the voltage is restored after voltage failure. For compressors leaving the factory, this function is made inactive. If desired, the function can be activated. Consult the Atlas Copco Customer Centre. If activated and provided the regulator was in the automatic operation mode, the compressor will automatically restart if the supply voltage to the module is restored.
  • Page 72: Control Panel

    Instruction book Control panel Elektronikon regulator Control panel Parts and functions Reference Designation Function Display Shows the compressor operating condition and a number of icons to navigate through the menu. Pictograph Automatic operation Pictograph General alarm General alarm LED Flashes if a shut-down warning condition exists. Pictograph Service Service LED...
  • Page 73: Icons Used

    Instruction book Icons used Status icons Name Icon Description Stopped / Running When the compressor is stopped, the icon stands still. When the compressor is running, the icon is rotating. Compressor status Motor stopped Running unloaded Running loaded Machine control mode Local start / stop Remote start / stop Network control...
  • Page 74 Instruction book Input icons Icon Description Pressure temperature Digital input Special protection System icons Icon Description Compressor element (LP, HP, ...) Dryer Frequency converter Drain Filter Motor Failure expansion module Network problem General alarm 2920 7090 51...
  • Page 75 Instruction book Menu icons Icon Description Inputs Outputs Alarms (Warnings, shutdowns) Counters Test Settings Service Event history (saved data) Access key / User password Network Setpoint Info Navigation arrows Icon Description Down 2920 7090 51...
  • Page 76: Main Screen

    Instruction book Main screen Control panel Scroll keys Enter key Escape key Function The Main screen shows the status of the compressor operation and is the gateway to all functions implemented in the controller. The Main screen is shown automatically when the voltage is switched on and one of the keys is pushed. It is switched off automatically after a few minutes when no keys are pushed.
  • Page 77 Instruction book Text on figures Compressor Outlet Element Outlet (fixed speed compressors) Flow in % (compressors with frequency converter) Load (text varies upon the compressors actual condition) Menu Unload (text varies upon the compressors actual condition) • Section A shows information regarding the compressor operation (e.g. the outlet pressure (1), the temperature at the compressor outlet (2)).
  • Page 78: Calling Up Menus

    Instruction book Calling up menus Control panel Control panel Scroll keys Enter key Escape key Description When the voltage is switched on, the main screen is shown automatically (see section Main screen): • To go to the Menu screen, highlight the Menu button (3), using the Scroll keys. •...
  • Page 79: Inputs Menu

    Instruction book • Press the Escape key to return to the Main screen. Inputs menu Control panel Scroll keys Enter key Escape key Menu icon, Inputs Function To call up information regarding the actually measured data and the status of some inputs such as the emergency stop switch.
  • Page 80: Outputs Menu

    Instruction book Menu Regulation • Using the Scroll keys, move the cursor to the Inputs icon (see above, section Menu icon). • Press the Enter key. A screen similar to the one below appears: Text on figure Inputs Compressor outlet Element outlet Ambient air Emergency stop...
  • Page 81 Instruction book Menu icon, Outputs Function To call up information regarding the actual status of some outputs such as the condition of the Fan overload contact (on air cooled compressors), the Emergency stop contact, etc. Procedure Starting from the Main screen (see Main screen), •...
  • Page 82: Counters

    Instruction book Counters Control panel Scroll keys Enter key Escape key Menu icon, Counters Function To call up: • The running hours • The loaded hours • The number of motor starts • The number of hours that the regulator has been powered •...
  • Page 83: Service Menu

    Instruction book Menu Regulation • Using the Scroll keys, move the cursor to the Counters icon (see above, section Menu icon) • Press the Enter key. Following screen appears: Text on figure Counters Running hours Motor starts Load relay VSD 1-20 % rpm in % (the percentage of the time during which the motor speed was between 1 and 20 %) (compressors with frequency converter) The screen shows a list of all counters with their actual readings.
  • Page 84 Instruction book Menu icon, Service Function • To reset the service plans which are carried out. • To check when the next service plans are to be carried out. • To find out which service plans were carried out in the past. •...
  • Page 85 Instruction book Overview Text on figure Overview Running Hours (green) Real Time hours (blue) Reset Example for service level (A): The figures at the left are the programmed service intervals. For Service interval A, the programmed number of running hours is 4000 hours (upper row, green) and the programmed number of real time hours is 8760 hours, which corresponds to one year (second row, blue).
  • Page 86 Instruction book Service plan Level Running hours Real time hours Modify Modifying a service plan Dependant on the operating conditions, it can be necessary to modify the service intervals. To do so, use the Scroll keys to select the value to be modified. A screen similar to the one below appears: Press the Enter key.
  • Page 87: Setpoint Menu

    Instruction book Next service Level Running hours Actual In the example above, the A Service level is programmed at 4000 running hours, of which 0 hours have passed. History The History screen shows a list of all service actions done in the past, sorted by date. The date at the top is the most recent service action.
  • Page 88 Instruction book Text on figure Menu Regulation • Move the cursor to the Setpoint icon (see above, section menu icon) using the Scroll keys. • Press the Enter key. Following screen appears: Text on figure Regulation Unloading pressure 1 Loading pressure 1 Unloading pressure 2 Loading pressure 2 Modify...
  • Page 89: Event History Menu

    Instruction book • The upper and lower limit of the setting is shown in grey, the actual setting is shown in black. Use the ↑ or ↓ key of the Scroll keys to modify the settings as required and press the Enter key to accept. If necessary, change the other settings as required in the same way as described above.
  • Page 90: Modifying General Settings

    Instruction book • Using the Scroll keys, move the cursor to the Event History icon (see above, section Menu icon) • The list of last shut-down and emergency stop cases is shown. • Scroll through the items to select the desired shut-down or emergency stop event. •...
  • Page 91: Info Menu

    Instruction book • Using the Scroll keys, move the cursor to the Settings icon (see above, section menu icon). • Press the Enter key. Following screen appears: Text on figure General Language used Time Date Date format Modify • To modify, select the Modify button using the Scroll keys and press the Enter key. •...
  • Page 92: Week Timer Menu

    • Move the cursor to the action button Menu and press the Enter key. Following screen appears: • Using the Scroll keys, move the cursor to the Info icon (see above, section Menu icon). • Press the Enter key. The Atlas Copco internet address appears on the screen. 4.14 Week timer menu...
  • Page 93 Instruction book Scroll keys Enter key Escape key Menu icon, Week timer Function • To program time-based start/stop commands for the compressor • To program time-based change-over commands for the net pressure band • Four different week schemes can be programmed. •...
  • Page 94 Instruction book Week Timer Week Action Schemes Week Cycle Status Week Timer Inactive Remaining Running Time The first item in this list is highlighted in red. Select the item requested and press the Enter key on the controller to modify. Programming week schemes •...
  • Page 95 Instruction book Friday Saturday Sunday • A new window opens. The Modify action button is selected. Press the enter button on the controller to create an action. Monday Modify • A new pop-up window opens. Select an action from this list by using the Scroll keys on the controller. When ready press the Enter key to confirm.
  • Page 96 Instruction book Monday Start Save Modify • To adjust the time, use the Scroll keys on the controller and press the Enter key to confirm. Monday Start Save Modify • A pop-up window opens. Use the ↑ or ↓ key of Scroll keys to modify the values of the hours. Use the ← or →...
  • Page 97 Instruction book • Press the Escape key on the controller. The action button Modify is selected. Use the Scroll keys to select the action Save. Monday Start Save Modify • A new pop-up window opens. Use the Scroll keys on the controller to select the correct actions. Press the Enter key to confirm.
  • Page 98 Instruction book Week Action Scheme 1 Monday - Start Tuesday Wednesday Thursday Friday Saturday Sunday Press the Escape key on the controller to leave this screen. Programming the week cycle A week cycle is a sequence of 10 weeks. For each week in the cycle, one of the four programmed week schemes can be chosen.
  • Page 99 Instruction book Week 2 Week 3 Week 4 Modify Press twice the Enter key on the controller to modify the first week. • A new window opens. Select the action, example: Week Action Scheme 1 Week Cycle Week 1 Week Action Scheme 1 Week Action Scheme 2 Week Action Scheme 3 Modify...
  • Page 100 Instruction book Week Timer Week Week Timer Inactive Week 1 • Press the Escape key on the controller to leave this window. The status shows that week 1 is active. Week Timer Week Action Schemes Week Cycle Status Remaining Running Time •...
  • Page 101: Test Menu

    Instruction book Week Timer Week Action Schemes Week Cycle Status Remaining Running Time • This timer is used when the week timer is set and for certain reasons the compressor must continue working, for example, 1 hour, it can be set in this screen. This timer is prior to the Week Timer action. Week Timer Week action schemes Remaining Running Time...
  • Page 102: User Password Menu

    Instruction book Procedure Starting from the Main screen (see Main screen): • Move the cursor to the action button Menu and press the enter key (2), following screen appears: • Using the scroll keys (1), move the cursor to the test icon (see above, section Menu icon) •...
  • Page 103: Web Server

    Instruction book Menu icon, Password Function If the password option is activated, it is impossible for not authorized persons to modify any setting. Procedure Starting from the Main screen (see Main screen), • Move the cursor to the action button Menu and press the Enter key. Following screen appears: •...
  • Page 104 Instruction book Configuration of the network card • Go to My Network places (1). • Click on View Network connections (1). • Select the Local Area connection (1), which is connected to the controller. 2920 7090 51...
  • Page 105 Instruction book • Click with the right button and select properties (1). • Use the checkbox Internet Protocol (TCP/IP) (1) (see picture). To avoid conflicts, de-select other properties if they are selected. After selecting TCP/IP, click on the Properties button (2) to change the settings. •...
  • Page 106 Instruction book • When using Internet Explorer: Open Internet Explorer and click on Tools - Internet options (2). • Click on the Connections tab (1) and then click on the LAN settings button (2). • In the Proxy server Group box, click on the Advanced button (1). 2920 7090 51...
  • Page 107 Instruction book • In the Exceptions Group box, enter the IP address of your controller. Multiple IP addresses can be given but they must be separated with semicolons (;). Example: Suppose that you already added two IP addresses (192.168.100.1 and 192.168.100.2). Now you add 192.168.100.100 and separate the 3 IP addresses by putting semicolons between them (1) (see picture).
  • Page 108 Instruction book Navigation and options • The banner shows the compressor type and the language selector. In this example, three languages are installed on the controller. • On the left site of the interface you can find the navigation menu (see picture below). If a license for ESi is foreseen, the menu contains 3 buttons.
  • Page 109 Instruction book Compressor settings All compressor settings can be hidden or shown. Put a mark for each setting. Only the machine status is fixed and can not be removed from the main screen. Analog inputs (The units of measure can be changed in the preference button from the navigation menu). Counters Counters give an overview of all actual counters from controller and compressor.
  • Page 110 Instruction book Digital outputs Shows a list of all digital outputs and their status. Special protections Give an overview of all special protections of the compressor. Service plan Shows all levels of the service plan and status. This screen only shows the running hours. It is also possible to show the actual status of the service interval.
  • Page 111: Programmable Settings

    Instruction book A possible ESi screen 4.18 Programmable settings Parameters: unloading/loading pressures for compressors without built-in refrigeration dryer Minimum Factory Maximum setting setting setting Unloading pressures Unloading pressure (7.5 bar compressors) bar(e) Unloading pressure (7.5 bar compressors) psig 101.5 108.8 Unloading pressure (8.5 bar compressors) bar(e) Unloading pressure (8.5 bar compressors)
  • Page 112 Instruction book Minimum Factory Maximum setting setting setting Loading pressure (13 bar compressors) psig 172.6 187.1 Loading pressure (100 psi compressors) bar(e) Loading pressure (100 psi compressors) psig 91.4 105.9 Loading pressure (125 psi compressors) bar(e) Loading pressure (125 psi compressors) psig 130.5 Loading pressure (150 psi compressors)
  • Page 113 The built-in service timers will give a Service warning message after their respective preprogrammed time interval has elapsed. Also see section. Consult Atlas Copco if a timer setting has to be changed. The intervals must not exceed the nominal intervals and must coincide logically. See section Modifying general settings.
  • Page 114 Minimum stop Once the compressor has automatically stopped, it will remain stopped for the minimum time stop time, whatever happens with the net air pressure. Consult Atlas Copco if a setting lower than 20 seconds is required. Unloading/ The regulator does not accept inconsistent settings, e.g. if the unloading pressure is Loading pressure programmed at 7.0 bar(e) (101 psi(g)), the maximum limit for the loading pressure changes...
  • Page 115: Osd Oil/Condensate Separator (Optional)

    Instruction book OSD oil/condensate separator (optional) OSD unit Oil/condensate separators Compressed air leaving oil-injected compressors contains oil. During cooling of this air, oil-containing condensate is formed. OSD are designed to separate the major part of this oil from the condensate and to catch the oil in a collector.
  • Page 116: Operating And Maintenance Instructions

    Instruction book Operation Condensate containing fine oil droplets flows via a strainer (5) through filter (3), in which the droplets coalesce into larger drops. The condensate is then led to vessel (1) where the oil rises due to the difference in specific mass.
  • Page 117: Pictographs

    Instruction book Condensate drains Maintenance instructions Consult section OSD unit for the references. Interval Running hours Operation Weekly Check pressure gauge (2). If the pressure reaches 2 bar(e) (29 psig) or every 6000 operating hours, replace filter (3): Unscrew the filter. Fill the new filter with water, lightly oil its gasket, screw it on and tighten by hand (approx.
  • Page 118 Instruction book Reference Description Consult instruction book before maintenance or repair 2920 7090 51...
  • Page 119: Installation

    Instruction book Installation Dimension drawings Drawings GA 5 up to GA 11 Pack, Floor mounted 2920 7090 51...
  • Page 120 Instruction book GA 5 up to GA 11 Pack on 270 l air receiver 2920 7090 51...
  • Page 121 Instruction book GA 5 up to GA 11 Full-Feature, Floor mounted 2920 7090 51...
  • Page 122 Instruction book GA 5 up to GA 11 Full-Feature on 270 l air receiver 2920 7090 51...
  • Page 123 Instruction book GA 5 up to GA 11 Pack on 500 l air receiver 2920 7090 51...
  • Page 124 Instruction book GA 5 up to GA 11 Full-Feature on 500 l air receiver Reference Designation Compressor and motor cooling air inlet Dryer cooling air outlet Dryer air inlet Compressed air outlet Compressor air inlet 2920 7090 51...
  • Page 125: Installation Proposal

    Outdoor/altitude operation If the compressor is installed outdoors or if the air inlet temperature can be below 0 ˚C (32 ˚F), precautions must be taken. In this case, and also if operating above 1000 m (3300 ft), consult Atlas Copco. Moving/lifting To transport the compressor with a forklift truck, use the openings in the frame.
  • Page 126 Instruction book Installation proposal Compressor room example Text on drawing Reference Designation Ventilation proposals Minimum free area to be reserved for the compressor installation 2920 7090 51...
  • Page 127: Installation Guidelines

    5. The drain pipes to the drain collector must not dip into the water of the drain collector. Atlas Copco has oil/water separators (type OSD) to separate the major part of the oil from the condensate to ensure that the condensate meets the requirements of the environmental codes.
  • Page 128: Electrical Connections

    Instruction book . If oil vapours and odours are undesirable, a QD type filter should be installed downstream of the PD filter. It is recommended to provide by-pass pipes and valves across the filters in order to isolate the filters during maintenance without disturbing the compressor.
  • Page 129 Connect the power supply cables to terminals L1, L2 and L3 (1X0) and the neutral conductor (if applicable) to terminal (N). Connect the earth conductor. Specific instructions for GA 5 up to GA 11 with 208 V/ 230 V / 460 V cubicle Always disconnect the power supply before working on the electrical circuit! The standard voltage configuration for the compressor is mentioned on the data plate of the machine.
  • Page 130 Instruction book To modify the wiring for an operating voltage of 208 V or 460 V, compressor main cubicle and transformer dryer cubicle should be rewired as described below: Required modifications in the compressor cubicle: Step Action Adjust the motor overload (FM1) setting. Rewire the control transformer (T1).
  • Page 131 Instruction book Adjustment screw of the motor overload Motor overload (FM1) setting GA 5 GA 7 GA 11 208 V 33.0 43.0 61.0 230 V (standard factory setting) 30.0 39.0 55.0 460 V 15.0 19.0 27.5 To rewire the control transformer (T1), move the wire of the transformer to the terminal marked with the desired voltage (208 V, 230 V or 460 V).
  • Page 132 The Elektronikon regulator is provided with an auxiliary relay (K05) for remote indication of a shutdown. Maximum load for the contacts: 10 A / 250 V AC. Stop the compressor and switch off the voltage before connecting external equipment. Consult Atlas Copco. Compressor status indication on compressors equipped with an Elektronikon® Graphic controller The Elektronikon regulator is provided with auxiliary contacts (K05, K07 and K08) for remote indication of: •...
  • Page 133: Pictographs

    39 of terminal (2x27) (input DIO4 on the controller). This results in loading and unloading of the compressor at the closing and opening pressures of the external pressure switch respectively. • LAN control: The compressor is controlled via a local network. Consult Atlas Copco. See section Electrical system to locate the connectors.
  • Page 134 Instruction book Reference Designation Warning: before connecting compressor electrically, consult Instruction book for motor rotation direction Torques for steel (Fe) or brass (CuZn) bolts Consult instruction book before greasing Lightly oil gasket of oil filter, screw it on and tighten by hand (approx. half a turn) 2920 7090 51...
  • Page 135: Operating Instructions

    Instruction book Operating instructions Initial start-up Safety The operator must apply all relevant Safety precautions. Procedure For the position of the air outlet valve and the drain connections, see sections Introduction Condensate system. 1. Consult the sections Electric cable size,Installation proposals Dimension drawings 2.
  • Page 136 Position of oil level sight-glass 8. Provide labels, warning the operator that: • The compressor may automatically restart after voltage failure (if activated, consult Atlas Copco). • The compressor is automatically controlled and may be restarted automatically. 2920 7090 51...
  • Page 137: Before Starting

    Instruction book • Affix the above sheet explaining the procedure for checking the motor rotation direction to the cooling air outlet of the compressor. • Check the rotation direction of the motor using the sheet. If the motor rotation direction is correct, the sheet on the top grating will be blown upwards.
  • Page 138: Starting

    Instruction book Starting Procedure For the position of the air outlet valve and the drain connections, see sections Introduction Condensate system Control panel of the Elektronikon® controller Control panel of the Elektronikon® Graphic controller Step Action Switch on the voltage. Check that voltage on LED (6) lights up. Open the air outlet valve.
  • Page 139: During Operation

    Instruction book During operation Procedure Control panel of the Elektronikon® controller Control panel of the Elektronikon® Graphic controller 2920 7090 51...
  • Page 140 Instruction book Position of oil level sight-glass and service indicator Regularly check the oil level: Approximately three minutes after stopping, sight-glass (Gl) should be between 1/4 and 3/4 full. If the level is too low, stop the compressor, wait until the compressor has stopped, depressurise the oil system by unscrewing oil filler plug (FC) one turn and wait a few minutes.
  • Page 141: Checking The Display

    Instruction book Checking the display Procedure Control panel of the Elektronikon® controller Control panel of the Elektronikon® Graphic controller Compressors with Elektronikon® controller: Check the display (2) regularly for readings and messages. The display normally shows the compressor outlet pressure, while the status of the compressor is indicated by pictographs. Remedy the trouble if alarm LED (7) is lit or flashes, see section Shutdown warning Shutdown...
  • Page 142: Stopping

    Instruction book Stopping Elektronikon regulator Control panel of the Elektronikon® controller Control panel of the Elektronikon® Graphic controller Air outlet valve 2920 7090 51...
  • Page 143: Taking Out Of Operation

    Instruction book Condensate drain valve, Tank-mounted GA 5 up to GA 11 Procedure Step Action Press stop button (9). Automatic operation LED (8) goes out and the compressor stops after 30 seconds of unloaded operation. To stop the compressor in the event of an emergency, press emergency stop button (10).
  • Page 144 Instruction book Step Action Drain the condensate circuit and disconnect the condensate piping from the condensate net. Air outlet valve Condensate drain valve, Tank-mounted GA 5 up to GA 11 2920 7090 51...
  • Page 145: Maintenance

    For overhauling or carrying out preventive maintenance, service kits are available (see section Service kits). Service contracts Atlas Copco offers several types of service contracts, relieving you of all preventive maintenance work. Consult your Atlas Copco Customer Centre. General When servicing, replace all removed gaskets, O-rings and washers.
  • Page 146 Instruction book Service plans for compressors with an Elektronikon® Graphic controller Besides the daily and 3-monthly checks, preventive service operations are specified in the schedule below. Each plan has a programmed time interval at which all service actions belonging to that plan are to be carried out.
  • Page 147 (2): or every 2 years, whichever comes first Test button on the EWD Important • Always consult Atlas Copco if a service timer setting has to be changed. • For the change interval of oil and oil filter in extreme conditions, consult your Atlas Copco Customer Centre.
  • Page 148: Oil Specifications

    It is strongly recommended to use genuine Atlas Copco Lubricants. They are the result of years of field experience and research in our labs. See section Preventive maintenance schedule for replacement intervals and section Service Kits for part number information.
  • Page 149: Service Kits

    Service kits For overhauling and for preventive maintenance, a wide range of service kits is available. Service kits comprise all parts required for servicing the component and offer the benefits of genuine Atlas Copco parts while keeping the maintenance budget low.
  • Page 150: Adjustments And Servicing Procedures

    Instruction book Adjustments and servicing procedures Drive motor General Keep the outside of the electric motor clean for efficient cooling. If necessary, remove dust with a brush and/ or compressed air jet. Bearing maintenance The motor bearings are greased for life. Air filter Location of air filter Air filter...
  • Page 151: Oil And Oil Filter Change

    Instruction book Oil and oil filter change Warning The operator must apply all relevant Safety precautions. Procedure Oil system components 1. Run the compressor until warm. Stop the compressor. Close the air outlet valve and switch off the voltage. Depressurise the compressor by opening manual drain valve(s) (Dm, Dm1). Wait a few minutes and depressurise the air receiver/oil (AR) tank by unscrewing oil filler plug (FC) just one turn to permit any pressure in the system to escape.
  • Page 152: Oil Separator Change

    Instruction book Add oil until the sight-glass (Gl) is 3/4 full. Tighten the filler plug. 8. Reset the service warning after carrying out all service actions in the relevant Service Plan: For compressors with Elektronikon® controller, see section Calling up/resetting the service timer.
  • Page 153: Coolers

    • Next, clean with an air jet in the reverse direction to normal flow. Use low pressure air. If necessary, the pressure may be increased up to 6 bar(e) (87 psig). • If it is necessary to wash the coolers with a cleaning agent, consult Atlas Copco. Belt tensioning and replacement...
  • Page 154 Refit the bodywork panels. Replacing the belts The belts must always be replaced as a set, even if only one of the belts is worn. Only use genuine Atlas Copco belts. Step Action Stop the compressor, close the air outlet valve and switch off the voltage.
  • Page 155: Safety Valves

    Instruction book Step Action Refit the bodywork panels. Check the belt tension after 50 running hours and adjust if necessary. Safety valves Location of safety valve Safety valve on oil separator vessel Safety valve on oil separator vessel 2920 7090 51...
  • Page 156: Dryer Maintenance Instructions

    Instruction book Safety valve on compressed air vessel Testing Before removing the valve, depressurise the compressor. See section Problem solving. Valve (SV) can be tested on a separate air line. If the valve does not open at the set pressure stamped on the valve, it needs to be replaced.
  • Page 157 Instruction book Local legislation Local legislation may stipulate that: • Work on the refrigerant circuit of the cooling dryer or on any equipment which influences its function must be undertaken by an authorised control body. • The installation should be checked once a year by an authorised control body. General For all references see section Introduction.
  • Page 158: Problem Solving

    Instruction book Problem solving Warning Before carrying out any maintenance, repair work or adjustment, press the stop button, wait until the compressor has stopped, press the emergency stop button and switch off the voltage. Close the air outlet valve and lock it if necessary. If provided, open the manual condensate drain valves.
  • Page 159 Oil cooler clogged Clean cooler Thermostatic bypass valve Have valve tested malfunctioning Air cooler clogged Clean cooler Compressor element out of order Consult Atlas Copco Customer Centre Oil filter clogged Replace Dryer For all references hereafter, consult section dryer. 2920 7090 51...
  • Page 160 Instruction book Condition Fault Remedy Pressure dewpoint too high Air inlet temperature too high Check and correct; if necessary, clean the aftercooler of the compressor Ambient temperature too high Check and correct; if necessary, draw cooling air via a duct from a cooler place or relocate the compressor Shortage of refrigerant Have circuit checked for leaks and...
  • Page 161: Technical Data

    Instruction book Technical data 11.1 Readings on display Elektronikon Control panel of the Elektronikon® controller Control panel of the Elektronikon® Graphic controller Important The readings mentioned below are valid under the reference conditions (see section Reference conditions and limitations). Reference Reading Air outlet pressure Modulates between programmed unloading and loading pressures.
  • Page 162: Electric Cable Size

    Instruction book 11.2 Electric cable size Important warning The compressor is delivered with 3 m (10 ft.) cable and cable gland. This cable gland is necessary to ensure the protection degree of the electric cubicle and to protect its components from dust from the environment. •...
  • Page 163 If the local conditions are more severe then the described standard conditions, the cables and fuses for worst case conditions should be used. Cable size Type Approval Recommended wire section (mm Pack Full Feature GA 5 4 x 6 4 x 10 GA 5 4 x 6 4 x 10 GA 5 4 x 2.5...
  • Page 164: Settings For Overload Relay And Fuses

    Instruction book Type Approval Recommended wire section (AWG) Pack Full Feature GA 5 CSA/UL GA 5 200/230/460 CSA/UL GA 5 CSA/UL GA 7 CSA/UL GA 7 200/230/460 CSA/UL GA 7 CSA/UL GA 11 CSA/UL GA 11 200/230/460 CSA/UL GA 11 CSA/UL 11.3 Settings for overload relay and fuses...
  • Page 165: Dryer Switches

    GA 11 400 + N GA 11 GA 11 Type Approval Overload Fuse rating (A) setting (FM1) Class J or RK Pack Full Feature GA 5 CSA/UL 34.5 GA 5 200/230/460 CSA/UL 33/30/15 40/40/20 40/40/20 GA 5 CSA/UL GA 7 CSA/UL 44.5...
  • Page 166: Compressor Data

    ˚F 11.6 Compressor data Reference conditions All data specified below are valid at reference conditions, see section Reference conditions limitations. GA 5 Units 7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi Frequency...
  • Page 167 Instruction book Units 7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi Pressure drop over psig 1.45 1.16 0.72 1.45 1.16 0.72 dryer, Full-Feature units Motor shaft speed r/min 2900 2900 2900 2900 3510 3510 3510...
  • Page 168 Instruction book Units 7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi Oil capacity US gal 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 Oil capacity Imp gal 0.79 0.79 0.79 0.79 0.79 0.79 0.79 0.79...
  • Page 169 Instruction book Units 7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi Temperature of air ˚F leaving outlet valve (approx.) Temperature of air ˚C leaving outlet valve (approx.), Full- Feature units Temperature of air ˚F leaving outlet valve (approx.), Full-...
  • Page 170 Instruction book Units 7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi Maximum bar(e) 10.8 12.5 (unloading) pressure, units without dryer Maximum psig (unloading) pressure, units without dryer Maximum bar(e) 7.25 8.25 9.75 12.75 7.15 8.85...
  • Page 171: Technical Data Elektronikon® Controller

    Instruction book Units 7.5 bar 8.5 bar 10 bar 13 bar 100 psi 125 psi 150 psi 175 psi Dew-point, Full- ˚F 37.4 37.4 37.4 37.4 37.4 37.4 37.4 37.4 Feature units Nominal motor rating kW Nominal motor rating hp 14.75 14.75 14.75...
  • Page 172: Analog Inputs

    Instruction book Noise immunity IEC61000-6-2 Mounting Cabinet door Digital outputs Parameter Value Number of outputs 6 (Elektronikon® controller - p.n. 1900 5200 00 …. 1900 5200 9 ( Elektronikon® Graphic controller - p.n. 1900 5200 10 …. 1900 5200 19) Type Relay (voltage free contacts) Rated voltage AC...
  • Page 173: Instructions For Use

    Instruction book Instructions for use Oil separator vessel This vessel can contain pressurised air; this can be potentially dangerous if the equipment is misused. This vessel must only be used as a compressed air/oil separator tank and must be operated within the limits specified on the data plate.
  • Page 174: Guidelines For Inspection

    Instruction book Guidelines for inspection Guidelines On the Declaration of Conformity / Declaration by the Manufacturer, the harmonised and/or other standards that have been used for the design are shown and/or referred to. The Declaration of Conformity / Declaration by the Manufacturer is part of the documentation that is supplied with this compressor.
  • Page 175: Pressure Equipment Directives

    II and higher according to the Pressure Equipment Directive 97/23/EC and all pressure equipment according to the Simple Pressure Vessel Directive 87/404/EEC. Compressor type Part number Description PED Class GA 5 up to GA 11 2202 8891 01 Safety valve 2202 8891 03 Safety valve 2202 8891 02...
  • Page 176: Declaration Of Conformity

    Instruction book Declaration of conformity Typical example of a Declaration of Conformity document 2920 7090 51...
  • Page 178 Atlas Copco's pursuit of innovation never ceases, driven by our need for reliability and efficiency. Always working with you, we are committed to providing you the customized quality air solution that is the driving force behind your business.

This manual is also suitable for:

Ga 7Ga 11

Table of Contents