Quick Start Wizard

The Quick Start wizard groups together all the settings you need to configure for a simple
application. You can access it either via SIMATIC PDM, or via the handheld programmer.
Do not use the Quick Start wizard to modify individual parameters (perform customization
for your application only after the Quick Start has been completed).

1. Quick Start

1.1. Application Type
Options
Default: STEEL
1.2. Response Rate
Sets the reaction speed of the device to measurement changes in the target range.
Options
Default: FAST
Use a setting just faster than the maximum filling or emptying rate (whichever is
greater). Slower settings provide higher accuracy; faster settings allow for more level
fluctuation.
1.3. Units
Select the units for the Quick Start variables (high and low calibration point, and level,
distance, or space).
M, CM, MM, FT, IN
Options
Default: M
1.4. Operation
NO SERVICE
LEVEL
Options
SPACE
DISTANCE
Default: DISTANCE
Page 46
SITRANS LR260 (HART) – INSTRUCTION MANUAL
STEEL
Silo construction
CONCRETE
SLOW
0.1 m/minute
MED
1.0 m/minute
FAST
10.0m/minute
Stops updating measurements and associated loop
current. Last valid measurement value is displayed.
Distance to material surface referenced from Low
Calibration Point (process empty level).
Distance to material surface referenced from High
Calibration Point (process full level).
Distance to material surface referenced from Sensor
Reference Point.
7ML19985KE02