Operation types
sensor reference point
(flange face)
low calibration point
1.5. Low Calibration Point (LOW CALIB. PT.)
Distance from Sensor Reference to Low Calibration Point: usually process empty
level. (See Operation types for an illustration.)
Values
1.6. High Calibration Point (HIGH CALIB. PT.)
Distance from Sensor Reference to High Calibration Point: usually process full level.
(See Operation types for an illustration.)
Values
Related parameters
When setting the High Calibration Point value, note that echoes are ignored within
Near Range (2.2.1.11).
1.7. Apply? (Apply changes)
In order to save the Quick Start settings it is necessary to select Yes and apply
changes.
YES, NO, DONE
Options
Display shows D D ONE when Quick Start is successfully completed.
Press M M ode
7ML19985KE02
SITRANS LR260 (HART) – INSTRUCTION MANUAL
high
calibration
point
distance
space
level
Range: 0.0000 to 30.000 m
Default: horn type dependent
Range: 0.0000 to 30.000 m
Default: 0.0 m
2.2. 1 .12. Near Range
to return to Measurement mode.