Fail-safe Timer

Fail-safe Timer determines the time to elapse after the last valid reading before a Fail-
safe state is activated. Fail-safe Material Level determines the level to be reported when
the Fail-safe timer expires. Upon receiving a reliable echo, the loss of echo condition is
aborted, the Service Required icon and error message are cleared, and the reading and
mA output return to the current level.

Fail-safe Material Level

2.4.1. Fail-safe Timer

When the
2.4.2. Fail-safe Material Level (FAILSAFE MAT. LE)
HI
LO
HOLD
VALUE

Fail-safe Level

When Fail-safe Material level is set to Value, the Fail-safe Level defines a user-defined
level to report when the Fail-safe timer expires..
Values
7ML19985KE02
SITRANS LR260 (HART) – INSTRUCTION MANUAL
expires, the material level to be reported is determined by
.
Fail-safe Material Level
Use Maximum mA Limit as material level
Use Minimum mA Limit as material level
Level remains at last reading
User-selected value as defined in Fail-safe Level
Fail-safe Level
3.6 to 22.6 mA
Page 97