The options are C C enter, CLEF (Constrained Leading Edge Fit), H H ybrid or R R ising Edge. C C LEF
uses the leading edge of the echo. It can be used to compensate for materials with a low
dK value, which may cause the vessel bottom to be reported as the level instead of the
actual material level, in low level conditions. C C LEF range is the level below which the
CLEF algorithm will be used: above this level the Center algorithm is used.
Hybrid uses a combination of C C enter and C C LEF, depending on the setting for CLEF range.

Auto False Echo Suppression

If an obstruction is causing a large echo before the material level echo, that echo will rise
above the default TVT curve and may be selected as the true echo. Auto False-Echo
Suppression modifies the TVT curve so that the false echo will not rise above the TVT
curve.
When you use Auto False Echo Suppression, the device first learns the echo profile at
1)
that moment
. A learned TVT curve follows the echo profile and rises above the false
echo. You set Auto Suppression Range so that the learned profile replaces the default
TVT curve up to a point past the obstruction. From that point on, the default TVT curve is
used. The material level echo rises above this, and is selected as the true echo.
Example after Auto False Echo Suppression
learned
TVT curve
false echo echo marker

Measurement Range

Near Range

2.2.1.12. Near Range
programs SITRANS LR260 to ignore the zone in front of the antenna.
The default blanking distance is 50 mm (1.97") from end of horn antenna.
Near Range allows you to increase the blanking value from its factory default. But
Auto False Echo Suppression
blanking distance from factory values.
1)
Use Auto False Echo Suppression when the material level is substantially lower than pro-
cess full level (ideally when the tank is empty or almost empty).
Page 94
SITRANS LR260 (HART) – INSTRUCTION MANUAL
level
is generally recommended in preference to extending the
2.2.5.2.