Siemens SITRANS LR260 Operating Instructions Manual page 51

Radar transmitters
Hide thumbs Also See for SITRANS LR260:
Table of Contents

Advertisement

To set Service/Calibration schedules:
1)
Open the menu D D evice – Maintenance, and click on the S S ervice/Calibration
Schedule tab.
2)
Modify desired values, and click on W W rite.
3)
Click on R R ead, to see the effects of your modification.
4)
If desired, activate alerts.
5)
Click on S S ervice Performed to reset the schedule.
Device Reset
Factory Defaults
Use D D evice Reset to reset all user parameters excluding device addresses, the parameter
block I I dentification, and Maintenance Schedule parameters to the default settings.
1.
Open the menu D D evice – Device Reset and click on O O K to perform a reset to Factory
Defaults.
2.
After the reset is complete, upload parameters to the PC/PG. (If you are performing a
reset after replacing the device with a different instrument, do not upload
parameters to the PC/PG).
Configuration Flag Reset
To reset the configuration flag to zero, open the menu D D evice – Configuration Flag Reset
and execute a reset.
D/A (Digital/Analog) Trim
Allows you to trim the 4 mA and 20 mA points in order to calibrate the mA output.
Open the menu D D evice – D/A Trim. You will be prompted to attach a calibrated meter and
enter the values at 4 mA and at 20 mA.
Select AnalogOut
Allows you to select one of three operation types:
level
space
distance
1)
Open the menu D D evice – Select AnalogOut.
2)
The S S elect AnalogOut window displays the current setting: click on O O K.
3)
Select the desired option, and click on O O K.
4)
The S S elect AnalogOut window displays the new setting: click on O O K.
7ML19985KE02
SITRANS LR260 (HART) – INSTRUCTION MANUAL
Page 43