vacon • 23
The returned value consists of six words (0x42 means Word, 0x06 is the number of values returned),
and the values are 0x01BA, 0x0002, 0x0197, 0x07DC, 0x0B5F, and 0x0001. Thus the following infor-
mation can be determined about the device:
• Manufacturer code is 0x01BA
• Drive Unit type is 0x0002
• Software version is 4.7 (0x0197 = 407d)
• Firmware date (year) is 2012 (0x07DC)
• Firmware date (day/month) is 29/11 (0x0B5F = 2911d)
• The device contains one axis
4.4.5.3
Requesting the value of drive parameter ID 103
The following information is used for this request:
Field
Request reference
Request ID
Axis number
No. of Parameters
Attribute
No. of Elements
Parameter Number
Subindex
The request from the master is:
PROFINET Write request
header
...
The slave acknowledges with a PROFINET write response header.
Table 29.
PROFINET Write response
header
...
The master reads the result of the operation from the drive using a PROFINET read request header.
Table 30.
PROFINET Read request
header
...
4
Table 27.
Contents
0x03
0x01 = Request parameter
0x01
0x01
0x10 = Value
0x01
0x2711 (10001d)
0x0067 (103d)
Table 28.
Request header
0x03 0x01 0x01 0x01
Commissioning
Parameter address
0x10 0x01 0x27 0x11 0x00
0x67
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205

Advertisement