Commissioning
4.4.5.2
Request all elements of PNU964 value
The following information is used for this request.
Field
Request reference
Request ID
Axis number
No. of Parameters
Attribute
No. of Elements
Parameter Number
Subindex
The request from the master is:
PROFINET Write request
header
...
The slave responds to the write request with a PROFINET write response header.
Table 24.
PROFINET Write response
header
...
The master reads the result of the operation from the drive using a PROFINET read request header.
Table 25.
PROFINET Read request
header
...
The slave responds to the read request:
PROFINET Read response
header
...
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Table 22.
Contents
0x02
0x01 = Request parameter
0x01
0x01
0x10 = Value
0x06
0x03C4 (964d)
0x0000 (0d)
Table 23.
Request header
0x02 0x01 0x01 0x01
Table 26.
Response header
0x02 0x01 0x01 0x01
Parameter address
0x10 0x06 0x03 0xC4 0x00
0x00
Parameter value
0x42 0x06 0x01 0xBA 0x00 0x02
0x01 0x97 0x07 0xDC 0x0B 0x5F
0x00 0x01
vacon • 22