Vacon 100 Installation Manual page 21

Integrated profinet io
Hide thumbs Also See for 100:
Table of Contents

Advertisement

Commissioning
4.4.3.2
PROFIdrive 4.1 error classes and code
Error class
0x0...0x9 =
reserved (not used)
0x0 = read error
0x1 = write error
0x2 = module failure
0xA = application
0x3...0x7 = reserved (not used)
0x8 = version conflict
0x9 = feature not supported
0xA...0xF = user-specific (not used)
0xB = access
0x0 = invalid index
0x1 = write length error
0x2 = invalid slot
0x3 = type conflict
0x4 = invalid area
0x5 = state conflict
0x6 = access denied
0x7 = invalid range
0x8 = invalid parameter
0x9 = invalid type
0xA...0xF = user-specific (not used)
0x0 = read constraint conflict
0xC = resource
0x1 = write constraint conflict
0x2 = resource busy
0x3 = resource unavailable
0x4...0x7 = reserved (not used)
0x8...0xF = user-specific (not used)
0xD...0xF = user-
specific (not used)
4.4.3.3
PROFIdrive Parameter Access errors
In addition to the error indications in the error response field, details about the error are provided
in the parameter value field. The third octet in the parameter value is set to 0x00 and the fourth oc-
tet is assigned the error number, as described in the table below (continued on next page).
Error
number
0x00
Impermissible parameter number
0x01
Parameter value cannot be changed
0x02
Low or high limit exceeded
0x03
Invalid subindex
0x04
Non-array parameter
0x05
Incorrect data type
24-hour support +358 (0)201 212 575 • Email: vacon@vacon.com
Table 14.
Error codes
Table 15.
Meaning
PROFIdrive meaning
0xB0 = parameter requests are not
supported.
0xB5 = parameter access is temporarily
not possible due to internal processing
status.
0xB7 = Write request with error in the
parameter request header.
When used
Access to unavailable parameter.
Change request to a read-only parameter.
Change request which exceeds parameter
value range.
Access to an unavailable subindex of an
array parameter.
Attempt to access subindex of a non-array
parameter.
Change request containing invalid data
type for the accessed parameter.
vacon • 18
4

Advertisement

Table of Contents
loading

Table of Contents