5.31.1
Factory Default Main Panel (Hardware)
Step 1 - Remove AC and battery from the panel.
Step 2 - Remove all wires from the Zone 1 and PGM1 terminals.
Step 3 - With a piece of wire short the Zone 1 terminal to the PGM1 terminal.
Step 4 - Apply AC power to the main panel.
Step 5 - When Zone Light 1 is lit on the keypad the default is complete.
Step 6 - Remove AC power from the control
Step 7 - Reconnect all original wiring and power up the control.
AC power must be used to power the panel. The panel will not default if the battery is used.
5.31.2
Factory Default Main Panel (Software) and other Modules
Step 1 - Enter the Installer Programming mode.
Step 2 - Enter Program Section [XXX].
Step 3 - Enter the Installer Code.
Step 4 - Enter Program Section [XXX] again.
The panel will take a few seconds to perform the default. When the keypad is again operational the default is
complete.
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Restore Main Panel (Software) to Factory Default Programming ....... Section [999]
Restore Escort5580 to Factory Default Programming ........................ Section [995]
Restore PC5132 to Factory Default Programming ............................. Section [996]
Restore PC5400 to Factory Default Programming ............................. Section [997]
Restore PC5928 to Factory Default Programming ............................. Section [998]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
5.32
Installer Lockout
If Installer Lockout is selected a hardware default cannot be performed. If a software default is performed
all programming will restore to factory default.
When Installer Lockout Disable is selected the panel will restore all programming to factory defaults if a
hardware or software default is performed on the main control panel.
To enable or disable Installer Lockout perform the following:
Step 1 - Enter Installer Programming
Step 2 - Enter Program Section [XXX]
Step 3 - Enter the Installer Code.
Step 4 - Enter Program Section [XXX] again.
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Installer Lockout Enable ................................ Section [990]
Installer Lockout Disable ............................... Section [991]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
5.33
Walk Test (Installer)
The Installer Walk Test can be used to verify that each zone of the panel is working. To perform a Walk
Test, enter the following:
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]
When any zone is violated the panel will activate the Bell Output for two seconds, log the event to the
Event Buffer and communicate the alarm to central station.
To stop the test, you must do the following:
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]