Force Arm Enable (Shall not be enabled on UL Listed systems)
Determines if the system can be armed with the zone violated. At the end of exit delay, if this type of zone
is violated, it will be ignored by the panel. Once the zone is secured it will be added back into the system.
This zone attribute is useful for a garage door. The customer can arm the system with the garage door
open. Later when the customer closes the door it becomes part of the system.
NOTE: 24-hour zones must not have Force Arm enabled.
Swinger Shutdown Enable (Shall not be enabled on UL Listed systems)
Determines if the panel will shut down the communicator for the zone after the swinger limit is reached (See
Section 5.17 "Swinger
Transmission (TX) Delay Enable
Determines if the panel will delay communicating the alarm reporting code to the central station (See
Section 5.18 "Transmission Delay").
Wireless Zone
Determines if the zone is a wireless zone or a hardwired zone. Allows the panel to generate low battery
trouble and zone supervisories.
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Zones 1 to 32 Attributes ................................ Section [101] - [132]
Audible/Silent Alarm ...................................... Section [101] - [132], Option [1]
Pulsed/Steady Alarm ..................................... Section [101] - [132], Option [2]
Activate Chime ............................................... Section [101] - [132], Option [3]
Bypass Enable ............................................... Section [101] - [132], Option [4]
Force Arm Enable .......................................... Section [101] - [132], Option [5]
Swinger Shutdown Enable ............................ Section [101] - [132], Option [6]
Transmission Delay Enable ............................ Section [101] - [132], Option [7]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
5.3
Communicator - Dialing
If the Communicator Disable option is selected the panel will not attempt to call central station. If enabled
the panel will attempt to call central station when an event occurs that has a valid reporting code
programmed (See
Communicator Call Direction Options are used to select which phone number the panel will dial when an
event occurs.
If DTMF Dialing is enabled the panel will dial using DTMF (touch tone). If Switch to Pulse Dial is enabled
the panel will switch to pulse dialing on the 5th attempt to call the central station. If disabled the panel will
always dial DTMF.
If DTMF Dialing is disabled the panel will always pulse dial.
The Post Dial Wait for Handshake determines the amount of time the panel will wait for a valid
handshake from the receiver. If the panel does not hear the handshake it will consider the call a failed
attempt, hang up and try again.
The Maximum Dialing Attempts determines the maximum number of attempts the panel will make to
send a signal to the central station before indicating a Failure to Communicate (FTC) trouble condition.
The 3rd Phone Number can be used to back up the 1st in this situation (See
Phone
Numbers").
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Pulse Dialing .................................................. Section [380], Option [3]
Switch to Pulse Dial ....................................... Section [380], Option [4]
Post Dial Wait for Handshake ........................ Section [161]
Maximum Dialing Attempts ............................ Section [160]
Communicator Disable .................................. Section [380], Option [1]
Communicator Call Direction Options ............ Section [361] to [368]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
5.4
Communicator - Phone Numbers
The panel can call 3 different phone numbers for communication to central station. The 1st Phone
Number is the primary number, the 2nd Phone Number is the secondary number and the 3rd Phone
Number will back up the 1st phone number if enabled.
The 3rd Phone Number will NOT back up the 2nd Phone Number.
If Alternate Dial is enabled the panel will alternate between the 1st and 3rd phone numbers when
attempting to call the central station. If disabled the panel will only attempt to call the 3rd phone number
after failing to communicate on the 1st phone number.
For Alternate Dial to work properly the 3rd Phone Number must be enabled.
R
A
M
D
Shutdown") .
Section 5.7 "Communicator - Reporting
E
S
C
R
I
Code").