5.7.6
Priority/Emergency
The panel will transmit a Keypad Fire Alarm Reporting Code AND the Keypad Fire Restoral Reporting
Code when the Fire Keys on any keypad is pressed for two seconds.
The panel will transmit a Keypad Auxiliary Alarm Reporting Code AND the Keypad Auxiliary Restoral
Reporting Code when the Auxiliary Keys on any keypad is pressed for two seconds.
The panel will transmit a Keypad Panic Alarm Reporting Code AND the Keypad Panic Restoral
Reporting Code when the Panic Keys on any keypad is pressed for two seconds.
The panel will transmit a Duress Reporting Code any time either Duress Code is entered at any keypad. If
the panel is armed using the Duress Code the panel will also transmit a Closing by Duress Reporting
Code or if the panel is disarmed it will also transmit an Opening by Duress Reporting Code.
If PGM2 is being used for two wire smoke detectors (See
a Two Wire Smoke Alarm Reporting Code if a smoke detector goes into alarm. The panel will transmit the
Two Wire Smoke Alarm Restoral Reporting Code when the zone is restored.
5.7.7
Maintenance
The panel will transmit a Battery Trouble Alarm Reporting Code when the backup battery drops below
11.5 V
. The Battery Trouble Restoral Reporting Code will not be transmitted until the battery has been
DC
charged over 12.5 V
To prevent the panel from transmitting an AC Failure Trouble Alarm Reporting Code during short power
outages the panel will not send the signal unless AC power is lost for the amount of minutes programmed
for the AC Failure Communication Delay. The AC Failure Trouble Restoral Reporting Code will be
transmitted as soon as AC power is restored.
NOTE: If AC failure communications delay is programmed as 000, AC failure transmission will be
disabled.
A Bell Circuit Trouble Alarm Reporting Code will be transmitted immediately if an open condition is
measured on the Bell Output of the main panel. The Bell Circuit Trouble Restoral Reporting Code will be
transmitted as soon as the problem is corrected.
A Fire Trouble Alarm Reporting Code will be transmitted immediately when an open condition is
measured on any Fire type zone (See
Code will be transmitted as soon as the problem is corrected.
The Auxiliary Power Supply Trouble Alarm Reporting Code will be transmitted if the AUX output is
shorted. The AUX output control incorporates a fuseless design. When excessive current is drawn the
panel will automatically shut off the output. The panel will constantly check the AUX output and when the
excessive current draw is removed the panel will reset the output and transmit an Auxiliary Power Supply
Trouble Restoral Reporting Code.
A TLM Trouble Reporting Code can only be transmitted if a LINKS1000 Cellular Communicator is being
used (See
Section 5.26 "LINKS1000 Cellular
the time programmed for the TLM Trouble Delay. The TLM Restoral Reporting Code will be transmitted
within 10 seconds of the problem being corrected.
A General System Trouble Reporting Code will be transmitted if the panel detects any of the following on
the PC5204 Power Supply/Output Module: AC Power Failure, Low Battery, AUX Output Trouble, Output #1
Supervisory trouble or the PC5400 is off-line. The General System Trouble Restoral Reporting Code will
be transmitted when all of the listed problems are corrected.
A General System Supervisory Trouble Reporting Code will be transmitted if any module goes missing
from the Keybus. If the module is a zone expander the panel will also transmit the Zone Expander
Supervisory Alarm Trouble Reporting Code. The panel will send a General System Supervisory
Restoral Reporting Code when the problem is corrected as well as a Zone Expander Supervisory
Restoral Reporting Code if the module is a zone expander.
5.7.8
Test Transmissions
The panel can be programmed to transmit a Periodic Test Transmission Reporting Code (See
5.13 "Test
Transmissions") , a System Test Reporting Code (See
LINKS1000 Test Transmission Reporting Code (See
5.7.9
Wireless Maintenance
The panel will transmit a General Zone Low Battery Alarm Reporting Code if a low battery condition is
indicated by a detector. The transmission of the trouble will be delayed by the number of days
programmed for Zone Low Battery Transmission Delay. The General Zone Low Battery Restoral
Reporting Code will be transmitted when the problem is corrected. The specific zone that caused the
trouble will be stored to the Event Buffer.
The restoral will not be transmitted until all detectors indicate a good battery condition.
R
A
M
D
.
DC
Section 5.1 "Zone
E
S
C
R
I
Section 5.10 "PGM
Definitions"). The Fire Trouble Restoral Reporting
Communicator") . The panel will only transmit the signal after
Section 3.4 "[ ] Commands, [ ]
Section 5.26 "LINKS1000 Cellular
29
P
T
I
O
N
Outputs") the panel will send
Section