Table 5: Watchdog Status And The State Of The "Cpu Active" Led - Gamatronic Centric 3x480 Vac User Manual

Ups system
Hide thumbs Also See for Centric 3x480 Vac:
Table of Contents

Advertisement

Table 5: Watchdog status and the state of the "CPU Active" LED

S
TATE OF
"CPU A
" LED
CTIVE
There is normal communication
Steady GREEN
between the adaptor card
PC710A and the computer.
There is no communication
Blinking GREEN
between PC710A and the
computer.
The computer is in the process
of restarting, following
Blinking RED
programmatic activation of the
of the power button (PW_BN).
Activation of the power button
(PW_BN) failed to invoke an
orderly shutdown of the
Steady RED
computer, so a reset of the
computer has been effected via
the computer's reset button
(RST_SW).
There is no communication
between PC710A and the
OFF
computer, and the LED on the
computer motherboard
(internal) is OFF.
7.2.1.6.4
R
EMOTE MONITORING PANEL
This function performs an LED test of the remote monitoring panel, if one is attached to the system.
Tap the Start button to begin the LED test. Tap the Stop button to end the LED test.
If the Stop button is not pressed, the LED test will end by itself automatically after two minutes.
For information about the connection and use of the remote monitoring panel, see the
Centric 3x480 UPS Installation Guide.
7.2.1.6.5
A
UDIO TEST
Tests the audible alarm.
7.2.1.6.6
U
PDATE
For technician's use only. Updates the controller software.
7.2.1.6.7
S
CREEN SAVER SETUP
Enables/disables the LCD panel's screen saver.
7.2.1.6.8
S
TART
For technician's use only.
28
G
E
AMATRONIC
S
CPU
TATE OF
/S
TOP DEBUG
I
L
LECTRONIC
NDUSTRIES
TD
T
ROUBLESHOOTING SUGGESTIONS
In this case, the state of the LED on the computer
motherboard (internal) has no special significance.
The LED on the computer motherboard (internal) indicates
that the computer is operating. One of the following
conditions may be interfering with communication:
The computer may be starting up.
The computer may have hung (frozen or looping).
There may be a problem with the computer's serial
port.
There may be a problem with the cable between
PC710A and the computer.
Card PC710A may be faulty.
Same as for "Blinking GREEN" above.
Same as for "Blinking GREEN" above, plus the following:
The wiring between PC710A and the power button
(PW_BN) may be faulty, leaving PC710A no
choice but to use the reset button (RST_SW).
There may be a problem with the input power for the
computer motherboard – either the power itself or the cable.
.