Table 9: Key To Figure 60 (The Status Screen) - Gamatronic Centric 3x480 Vac User Manual

Ups system
Hide thumbs Also See for Centric 3x480 Vac:
Table of Contents

Advertisement

I
D
TEM
ESCRIPTION
1
Navigation trail – shows how you arrived at this screen.
Voltage and amperage reading of each bypass input phase. Pressing the
2
input icon displays additional measurements for each bypass input phases.
UPS state (ON / OFF)
3
and mode (Normal [inverter] mode / Bypass mode / Battery mode / No output).
Load level, indicates the load on each output phases, as a percentage of maximum
4
capacity. The white vertical bars fill with colour from left to right as the load increases
on the phase.
Voltage and amperage readings for each phase of the rectifier input.
5
Pressing the
input phase.
This graphic represents the UPS power modules. Pressing this icon gives access to
detailed readings of each UPS module's ac input, ac output, dc current, status, and
6
nominal values.
Modules alarm icon. When present, indicates that there is an active alarm condition for
7
one or more of the UPS modules. To see the modules' status in detail, press the
"modules" icon and then press the "status" button at the bottom of the modules screen.
Static switch alarm icon. When present, indicates that there is an active alarm
8
condition for the static switch. To see the static switch status in detail, press the "static
switch" icon and then press the "detail" button.
Voltage and amperage reading for each phase of the inverter output.
9
Pressing the
inverter output phase.
Static switch. This icon indicates the source of the output power – whether it is from
the inverter or the bypass input.
This graphic is displayed when the output source is the inverter (normal mode and
battery mode):
10
This graphic is displayed when the output source is the bypass input (bypass mode):
Pressing the static switch icon displays the static switch detail screen.
80
G
E
AMATRONIC
LECTRONIC

Table 9: Key to Figure 60 (the Status screen)

rectifier input icon displays more detailed readings for each rectifier
inverter output icon displays the more detailed reading for each
I
L
.
NDUSTRIES
TD
CENTRIC 3x480, User Guide, rel. 1.7
bypass

Advertisement