Variable name
210 4x0210 Seconds On Battery
211 4x0211 Estimated Backup Time
212 4x0212 Estimated Charge
213 4x0213 DC Voltage positive
214 4x0214 DC Voltage Negative
215 4x0215 DC Voltage total
216 4x0216 Battery Current
217 4x0217 Battery Temperature
218 4x0218 Number of phases
219 4x0219 Inverter Frequency Line 1
220 4x0220 Inverter Voltage Line 1
221 4x0221 Inverter Current Line 1
222 4x0222 Inverter Power Line 1
223 4x0223 Inverter Apparent Power Line 1
224 4x0224 Inverter Frequency Line 2
225 4x0225 Inverter Voltage Line 2
226 4x0226 Inverter Current Line 2
227 4x0227 Inverter Power Line 2
228 4x0228 Inverter Apparent Power Line 2
229 4x0229 Inverter Frequency Line 3
230 4x0230 Inverter Voltage Line 3
231 4x0231 Inverter Current Line 3
232 4x0232 Inverter Power Line 3
233 4x0233 Inverter Apparent Power Line 3
234 4x0234 Charger Voltage Line 1
G
E
AMATRONIC
LECTRONIC
GET Values
Seconds
Only available during power failure, otherwise zero
Minutes
Only available during power failure and when the battery is fully charged (6 in 4x0209),
otherwise zero. This value is a rough approximation received by mathematical
calculations, and assumes new and healthy batteries of average VRLA type in initial fully
charged state.
0-100%
Mathematical calculation of battery charge in percents; will send 200 if no value has been
calculated
×10 Vdc
Divide the value by 10 for real measurement: 4051/10=405.1 Vdc
×10 Vdc
Divide the value by 10 for real measurement: 4051/10=405.1 Vdc
×10 Vdc
Divide the value by 10 for real measurement: 8102/10=810.2 Vdc
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
°C
Degrees centigrade
1 to 3
Number of the UPS phases (always 3 for current units)
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac