Gamatronic Centric 3x480 Vac User Manual page 64

Ups system
Hide thumbs Also See for Centric 3x480 Vac:
Table of Contents

Advertisement

Register
Variable name
260 4x0260 Output Voltage Line 2
261 4x0261 Output Current Line 2
262 4x0262 Output Power Line 2
263 4x0263 Output Apparent Power Line 2
264 4x0264 Output Power Factor Line 2
265 4x0265 Output Load Line 2
266 4x0266 Output Voltage Line 3
267 4x0267 Output Current Line 3
268 4x0268 Output Power Line 3
269 4x0269 Output Apparent Power Line 3
270 4x0270 Output Power Factor Line 3
271 4x0271 Output Load Line 3
272 4x0272 Bypass Frequency
273 4x0273 Bypass Voltage Line 1
274 4x0274 Bypass Current Line 1
275 4x0275 Bypass Apparent Power Line 1
276 4x0276 Bypass Voltage Line 2
277 4x0277 Bypass Current Line 2
278 4x0278 Bypass Apparent Power Line 2
279 4x0279 Bypass Voltage Line 3
280 4x0280 Bypass Current Line 3
281 4x0281 Bypass Apparent Power Line 3
282 4x0282 Active Alarms Count
Register
Variable name
301 4x0301 General Fault
G
E
AMATRONIC
LECTRONIC
GET Values
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
%
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
%
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
Active alarms, except for the ones marked "ignored" or "for log only" in the controller
configuration
GET Values
0: Alarm off
Any active alarm exists, except for the ones marked "ignored" or "for log only" in the
1: Alarm on
controller configuration
56
I
L
.
NDUSTRIES
TD
Remarks
Remarks
CENTRIC 3x480, User Guide, rel. 1.7