Figure 83: Structure Of Shutdown_Reason - Gamatronic Centric 3x480 Vac User Manual

Ups system
Hide thumbs Also See for Centric 3x480 Vac:
Table of Contents

Advertisement

5.
The field Shutdown_reason (bytes 94 and 93) contains the sum (boolean "OR") of all relevant alarm
codes for the module, for 3 minutes after the alarm event.
Bit
Hexadecimal
number
value when
"on"
(decimal)
0
01
1
02
2
04
3
08
4
10
5
20
6
40
7
80
8
100
9
200
10
400
11
800
12
1000
13
2000
14
4000
15
8000
CENTRIC 3x480, User Guide, rel. 1.7
G
E
AMATRONIC
LECTRONIC

Figure 83: Structure of Shutdown_reason

Table 15: Interpreting Shutdown_reason
Meaning when bit is "on"
Dc very low.
Input voltage.
12 V out of range.
Dc fault.
IGBT desaturation.
PFC temperature.
Inverter voltage out of range.
Pulse-by-pulse (PBP) protection, or inverter voltage blackout.
Inverter shutdown due to command.
Complete shutdown.
Lock after 7 times output relays OFF during 5 minutes, unlock after 5 hrs.
PLL of slave without data
Dc high.
Circulation.
Inverter overload.
Inverter temperature.
I
L
.