device which may suffer from high temperature when the
inverter is working. Do not install the inverter in airproof location
and keep enough space around the inverter.
★ The protective grounding must be connected to the ground. The
cross section of wire should not be less than 4mm
★ The wire connects between battery and inverter should be
shorter than 3m, the current density should be less than
3.5A/mm
longer than 3m, the current density should be reduced.
★ It is recommended that a fuse or breaker shall be installed
between a battery, a bypass and an inverter. The rated current
of the fuse or breaker shall be twice as much as that of the
inverter (it shall be the same as that of the bypass).
★ Do not connect the battery charger or similar devices to the
input terminal of the inverter.
★ Do not put the inverter close to the flooded lead-acid battery
because the sparkle in the terminals may ignite the hydrogen
released by the battery.
★ It‟s an off-grid inverter, if connect to the grid, the inverter may be
damaged.
★ This inverter can only be used singly, parallel connection or in
series will damage the inverters.
★ Do not touch the output terminal that the voltage is too high
when the inverter is working. The terminal connect the load
only, otherwise the inverter is damaged. If you connect the load,
the inverter must stop working.
★ When the voltage level and the output frequency were set, the
inverter make sure that the voltage and frequency are
consistent with the bypass.
★ Do not attempt to repair the fault inverter yourself, otherwise it
may lead to a serious accident. Please contact the
manufacture‟s engineer.