13.1.13.5
Value: BR kWh
Group
Statistics
Units
kWh
Related FW
3.0
Description
This value shows the sum of kWh transferred from the busR to busL.
N
:
OTE
The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set
statistics.
13.1.13.6
Value: M kVAhr E
Group
Statistics
Units
-
Related FW
3.0
Description
This value shows the sum of kVAhr transferred from the busR to busL.
N
:
OTE
The counter can be readjusted/reset from InteliMonitor menu Monitor -> Set
statistics.
13.1.13.7
Value: PulseCounter 1
Group
Statistics
Units
-
Related FW
3.0
Description
This is the value of PulseCounter #1 module. See the binary input
PulseCounter
13.1.13.8
Value: PulseCounter 2
Group
Statistics
Units
-
Related FW
3.0
NT
InteliMains
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013