the master and if it is switched off the next one will take the master role.
N
:
OTE
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
C
AUTION
If the controller which is set to MASTER in PriorAutoSwap function is in
Emerg.
will assume MASTER role.
12.2.8.3
Setpoint: Priority ctrl
Group
Pwr management
Range [units]
DISABLED, MASTER [-]
Related FW
3.0
Force value
YES
possible
Description
DISABLED
MASTER
12.2.8.4
Setpoint: #SysAMFstrtDel
Group
Pwr management
Range [units]
0 .. 600 [s]
Related FW
3.0
Description
System start delay between input
Management System. When input
decoupling relay, this setpoint adjusts the delay among the mains failure and
the emergency start of the gen-sets. If the MCB feedback is closed, Power
management is started with 1s delay after the input
NT
InteliMains
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp – June 2013
!
manual, priority autoswapping will not work and no other controller
IM-NT does not provide the AutoSwap functions for other
controllers.
At least one controller in the logical group has to be
selected as MASTER if some PriorityAuto Swapping
mode is enabled. Only the controller with lowest CAN
address becomes an active master, the other are ignored
by SLAVE controllers. The MASTER controller evaluates
the Priority changing for all other controllers in the group
and sends them the "forced" Priority values.
Sys start/stop
closing and start of Power
Sys start/stop
is controlled by mains
Sys start/stop
closing -
154
Need help?
Do you have a question about the IM-NT-BB and is the answer not in the manual?
Questions and answers