Environmental Specifications

Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (operating and
storage)
Acoustical Noise
EMI Supression
Electrostatic Discharge (ESD)
Immunity
System Efficiency at Full Unity
Power Factor Load and Nominal
Input Voltage
Note: The 208/600 systems use an
input isolation transformer
option that reduces system
efficiency.

Battery Specifications

These specifications are for batteries supplied by the UPS manufacturer in
line-up-and-match cabinets:
Battery Type
Nominal Battery String
Voltage
Float Charging
Equalizing Charge
Battery Charge Current
Limit
Powerware 9315 (200 kVA ---300 kVA) Operation

164201036 Rev. D 041500

0 to 40˚C without derating. However, operating
at or near 40˚C will adversely affect battery life
(refer to your battery specifications for more
information). The recommended operating
temperature is 25˚C.
Maximum 1500m (5000 ft) at 40_C without
derating
---20 to +70˚C (prolonged storage above 40˚C
will cause rapid battery self-discharge)
95% maximum noncondensing
65 dBA at a 1m distance
Meets FCC Regulation 47, Part 15, Subpart J, for
class A devices
Meets IEC 801---2 specifications. Withstands up
to 25 kV without damage and with no disturbance
or adverse effect to the critical load.
400V, 600V Models:
91%
480V Models:
92%
Sealed, maintenance-free, high rate discharge, lead-acid
cells
480 VDC (240 cells) for
420 VDC (210 cells) for
2.25 VDC per cell
(540 VDC based on 240 cells)
(470 VDC based on 210 cells)
2.40 VDC per cell, set to 2.25 VDC at factory
Limited to 25% of full, regardless of actual load on inverter
.