Product Specifications; System Input - Powerware 9315 Operation Manual

200 kva -- 300 kva
Hide thumbs Also See for 9315:
Table of Contents

Advertisement

both 50 Hz and 60 Hz, with various output power ratings. Smaller models within a
system may be upgraded in the field to larger models:
System
Powerware 9315 200
Powerware 9315 225
Powerware 9315 250
Powerware 9315 300
The following sections detail the input, output, environmental, and battery
specifications for the UPS.

System Input

Operating Input
Voltage
(Nominal +10/-- 15%)
Operating Input
Frequency Range
Operating Input
Current
Input Current
Harmonic Content
Power Walk-In
Power Factor
Line Surges
Powerware 9315 (200 kVA ---300 kVA) Operation
164201036 Rev. D 041500
The UPS systems are housed in freestanding, double-front cabinets
with safety shields behind the doors. The UPS systems are available in
Models
200 kVA
225 kVA
200 kVA & 250 kVA
225 kVA & 300 kVA
480 VAC for operation from 408 VAC to 528 VAC (60 Hz only)
400 VAC for operation from 340 VAC to 440 VAC (50/60 Hz only)
600 VAC for operation from 510 VAC to 660 VAC (60 Hz only)
3 Hz of nominal (50 Hz or 60 Hz)
Battery Charge:
125% of full load for overload + battery charge
Actual load + 25% of full load for battery charge
Reduced for Generator:
Adjustable, set to 102%
10% THD at full load (with input filter option installed)
Adjustable 3---60 second rectifier ramp-up to full utility load
Minimum 0.95
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801---4

Product Specifications

Notes
50 Hz or 60 Hz (400V models only)
60 Hz only
50 Hz or 60 Hz (400V models only)
60 Hz only
75