Normal Mode; Figure 3. Path Of Current Through The Ups In Normal Mode - Powerware 9315 Operation Manual

200 kva -- 300 kva
Hide thumbs Also See for 9315:
Table of Contents

Advertisement

Normal Mode

In Normal mode, utility AC power is supplied to the rectifier. The rectifier supplies
DC power to the inverter, which then supplies the critical load with AC power. The
rectifier also provides charging power to the battery. The battery charge condition
is monitored by the UPS and reported by a status indicator on the Monitor Panel.
The message "System Normal" appears in the status area of the LCD screen.
Figure 3 shows the path of electrical power through the UPS system when the UPS
is operating in Normal mode.
Bypass
Input
CB1
Rectifier
Input
Path of electrical power
If the utility AC power is interrupted or is out of specification, the UPS automatically
switches to Battery mode to support the critical load with no interruption. When
utility power returns, the UPS returns to Normal mode.
If the UPS system becomes overloaded, the UPS switches to Bypass mode. The
UPS automatically returns to Normal mode when the error condition is cleared and
system operation is restored within specified limits.
If the UPS suffers an internal failure, it switches automatically to Bypass mode and
remains in that mode until the failure is corrected and the UPS is back in service.
10
BYPASS
RECTIFIER
BATTERY

Figure 3. Path of Current Through the UPS in Normal Mode

K4
INVERTER
TRANSFORMER
Powerware 9315 (200 kVA ---300 kVA) Operation
Output
K3
(closed)
164201036 Rev. D 041500