Moxa Technologies DA-IRIGB-4DIO-PCI104-EMC4 User Manual page 7

Hide thumbs Also See for DA-IRIGB-4DIO-PCI104-EMC4:
Table of Contents

Advertisement

DA-IRIGB-4DIO-PCI104-EMC4 Module
Introduction
Surge Protection: 2 kV line-to-line and 4 kV line-to-ground surge protection, 8/20 µs waveform
Input Signals
IRIG-B: TTL or differential
Time Code Input
IRIG-B: Based on the IRIG STANDARD 200-04 and IEEE 1344
Precision and Accuracy
Accuracy (Time Synchronization): ±1 µs
Accuracy (Free Running): ±500 ms @ 24 hr
Timebase Precision: ±40 ns
Digital Input
Input Channels: 3, source type
Input Voltage: 0 to 30 VDC
Digital Input Levels for Dry Contacts:• Logic level 0: Close to GND
• Logic level 1: Open
Digital Input Levels for Wet Contacts:• Logic level 0: +3 V max.
• Logic level 1: +10 V to +30 V (source to DI)
Isolation: 3 kV optical isolation
Connector Type: DB9 male
Digital Output
Output Channels: 4, sink type
Output Current: Max. 200 mA per channel
On-state Voltage: 24 VDC nominal, open collector to 30 V
Isolation: 3 kV optical isolation
Connector Type: DB9
Operating Systems
Windows: Windows 7E
Linux: Debian 7
Physical Characteristics
Dimensions: 90 x 96 mm (3.54 x 3.78 in)
Environmental Limits
Operating Temperature: -10 to 60°C (14 to 140°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity: 5 to 95% (non-condensing)
Altitude: Up to 2000 m
Standards and Certifications
EMC: CE, FCC
EMI: EN 55032, EN 61000-3-2, EN 61000-3-3, FCC Part 15 Subpart B Class A
EMS: EN 55024, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC
61000-4-8, IEC 61000-4-11
Green Product: RoHS, CRoHS, WEEE
MTBF
(mean time between failures)
Time: 1,145,189 hrs
Database: Telcordia (Bellcore), GB
Power Requirements
Power Consumption: 2 W
Warranty
Warranty Period: 5 years