Electrical specifications

Input voltage (operable voltage
range) (V)
Frequency (Hz)
Number of phases, cabling
Steady-state current 100V/
200V
Current rating of breaker/fuse
(A)
Heat value (normal) (kJ/h)
Steady-state power (VA/W)
Power consumption (VA/W)
Notes:
106
Item
1
2
,
1.
The power current of Nx2 described in this table is required for a single power unit.
2.
If one power unit fails, another power unit requires electric current for the two power units.
Therefore, plan the power supply facility so that the current-carrying capacity for one power
unit can provide the total capacity for two power units.
3.
This table shows the power requirement (100 V or 200 V) for the maximum configuration .
The actual required power might exceed the value shown in the table when the tolerance is
included.
Electrical specifications for VSP G200
Hitachi Virtual Storage Platform G200 Hardware Reference Guide
Controller
AC 100-120/200-240
+6%/-11%
Single-phase with protective grounding
CBSS: 4.0x2/2.0x2
CBSL: 4.0x2/2.0x2
CBSS: 1800 or less
CBSL 1550 or less
3
CBSS: 800/760 or less
CBSL: 800/760 or less
CBSS: 520/500 or less
CBSL: 450/430 or less
Drive tray
SFF, LFF, FMD, and dense
intermix drive tray: AC 200-240
+6%/-11%
50/60 ±1
SFF drive tray: 2.4x2/1.2x2
LFF drive tray: 1.9x2/1.0x2
FMD drive tray: 2.6x2/1.3x2
Dense intermix drive tray: -/
3.0x2
16.0 (each electrical)
SFF drive tray: 1120 or less
LFF drive tray: 940 or less
FMD drive tray: 1300/1520 or
less
Dense intermix drive tray: 3460
or less
SFF drive tray: 480/460 or less
LFF drive tray: 380/350 or less
FMD drive tray: 520/490 or less
Dense intermix drive tray:
1200/1160 or less
SFF drive tray: 320/310 or less
LFF drive tray: 280/260 or less
FMD drive tray: 440/420 or less
Dense intermix drive tray:
1000/960 or less